Section 11. Programming Resource Library
115
11.4.1.2.1
Start Measurement Command (aMv!)
Qualifier
v
is a variable between 1 and 9. If supported by the sensor
manufacturer, v requests variant data. Variants may include:
•
alternate units (e.g. °C or °F)
•
additional values (e.g., level and temperature)
•
diagnostic of the sensor’s internal battery
Example:
Command:
5M!
Response: 500410 (atttnn, indicates address 5, data ready in 4 seconds, will
report 10 values).
Example:
Command:
5M7!
Response: 500201 (atttnn indicates address 5, data ready in 2 seconds, will
report 1 value).
v
= 7 instructs the sensor to return the voltage of its internal
battery.
11.4.1.2.2
Start Concurrent Measurement Command (aC!)
Concurrent measurement allows the CR200(X) to request a measurement,
continue program execution, and pick up the requested data on the next pass
through the program. The datalogger scan rate should be set such that the
resulting skew between time of measurement and time of data collection does
not compromise data integrity.
Note This command is new to Version 1.2 or higher of the SDI-12
Specification. Older sensors, older loggers, or new sensors that do not meet
v1.2 specifications will likely not support this command
11.4.1.2.3
Aborting a Measurement Command
A measurement command (
M!
or
C!
) is aborted when any other valid command
is sent to the sensor.
11.4.1.3 Send Data Commands (aDv! & aRv!)
11.4.1.3.1
Send Data Command (aDv!)
This command requests data from the sensor. It is normally issued
automatically by the datalogger after measurement commands
aMv!
or
aCv!
. In
transparent mode, the user asserts this command to obtain data. If the expected
number of data values are not returned in response to a
aD0!
command, the data
Summary of Contents for CR200
Page 32: ...Section 2 Quickstart Tutorial 22 ...
Page 45: ...Section 3 Overview 35 3 3 Specifications ...
Page 46: ...Section 3 Overview 36 ...
Page 58: ...Section 4 Sensor Support 48 ...
Page 62: ...Section 5 Measurement and Control Peripherals 52 ...
Page 78: ...Section 8 CR200 X Configuration 68 ...
Page 102: ...Section 9 Programming 92 ...
Page 138: ...Section 11 Programming Resource Library 128 ...
Page 156: ...Section 16 Support Software 146 ...
Page 160: ...Section 17 Care and Maintenance 150 ...
Page 167: ...Section 18 Troubleshooting 157 18 3 3 2 Charging Circuit Test Solar Panel ...
Page 168: ...Section 18 Troubleshooting 158 18 3 3 3 Charging Circuit Test Transformer ...
Page 169: ...Section 18 Troubleshooting 159 18 3 3 4 Adjusting Charging Circuit Voltage ...
Page 170: ...Section 18 Troubleshooting 160 ...
Page 184: ...Appendix A Glossary 14 ...
Page 190: ...Appendix B Status Table and Settings 20 ...
Page 192: ...Appendix C Serial Port Pin Outs 22 ...
Page 211: ......