Section 3. Overview
27
3.1.3.2
Voltage Outputs
Read More!
See
Control Output
(p. 49).
•
Switched Analog Output (Excitation)
: two channels (VX1/VX2) for
precise voltage excitation ranging from +2500 mV or +5000 mV. These
channels are regularly used with resistive bridge measurements. Each
channel will source up to 25 mA.
•
Digital I/O
: 2 channels (C1 - C2) configurable for on / off and pulse output
duration.
•
Switched 12 Volts (SW Battery)
: (switch on / off ) primary voltage under
program control for control of external devices requiring 12V DC, such as
humidity sensors. SW Battery can source up to 900 mA. See
TABLE.
Current Sourcing Limits
p. 38.
•
CR200(X) used as a PLC (programmable logic controller):
Utilizing
peripheral relays and analog output devices, the CR200(X) can manage
binary and variable control devices through the following output channels:
•
Digital I/O
: 2 channels (C1/C2) configurable for pulse output duration.
•
Switched 12 Volts (SW Battery)
: (switches on/off) primary voltage
under program control for control of external devices requiring 12V
DC, such as humidity sensors. SW Battery can source up to 900 mA.
See
TABLE. Current Sourcing Limits
p. 38.
3.1.3.3
Grounding Terminals
Read More!
See
Grounding
(p. 55).
Proper grounding will lend stability and protection to a data acquisition system.
It is the easiest and least expensive insurance against data loss-and the most
neglected. The following terminals are provided for connection of sensor and
datalogger grounding:
•
Signal Grounds
: 6 ground terminals ( ) used as reference for single-ended
analog inputs, pulse inputs, excitation returns, and as a ground for sensor
shield wires. Signal returns for pulse inputs should use terminals located
next to pulse inputs.
•
Power Grounds
: 6 terminals (G) used as returns for 5V, SW Battery, 12V,
and C1-C2 outputs. Use of G grounds for these outputs minimizes
potentially large current flow through the analog voltage measurement
section of the wiring panel, which can cause single-ended voltage
measurement errors.
•
Ground Lug
: 1 terminal ( ), the large ground lug is used to connect a
heavy gage wire to earth ground. A good earth connection is necessary to
secure the ground potential of the datalogger and shunt transients away
from electronics. Minimum 14 AWG wire is recommended.
Summary of Contents for CR200
Page 32: ...Section 2 Quickstart Tutorial 22 ...
Page 45: ...Section 3 Overview 35 3 3 Specifications ...
Page 46: ...Section 3 Overview 36 ...
Page 58: ...Section 4 Sensor Support 48 ...
Page 62: ...Section 5 Measurement and Control Peripherals 52 ...
Page 78: ...Section 8 CR200 X Configuration 68 ...
Page 102: ...Section 9 Programming 92 ...
Page 138: ...Section 11 Programming Resource Library 128 ...
Page 156: ...Section 16 Support Software 146 ...
Page 160: ...Section 17 Care and Maintenance 150 ...
Page 167: ...Section 18 Troubleshooting 157 18 3 3 2 Charging Circuit Test Solar Panel ...
Page 168: ...Section 18 Troubleshooting 158 18 3 3 3 Charging Circuit Test Transformer ...
Page 169: ...Section 18 Troubleshooting 159 18 3 3 4 Adjusting Charging Circuit Voltage ...
Page 170: ...Section 18 Troubleshooting 160 ...
Page 184: ...Appendix A Glossary 14 ...
Page 190: ...Appendix B Status Table and Settings 20 ...
Page 192: ...Appendix C Serial Port Pin Outs 22 ...
Page 211: ......