Section 7. Installation
110
these fluctuations by separating signal grounds (
) from power grounds (G).
To take advantage of this design, observe the following rules:
•
Connect grounds associated with 12V, SW12, 5V, and C1 – C8
terminals to G terminals.
•
Connect excitation grounds to the nearest
terminal on the same
terminal block.
•
Connect the low side of single-ended sensors to the nearest
terminal
on the same terminal block.
•
Connect shield wires to the
terminal nearest the terminals to which
the sensor signal wires are connected.
Note Several ground wires can be connected to the same ground
terminal.
If offset problems occur because of shield or ground leads with large current flow,
tying the problem leads into
terminals next to terminals configured for
excitation and pulse-count should help. Problem leads can also be tied directly to
the ground lug to minimize induced single-ended offset voltages.
7.3.3 Ground Potential Differences
Because a single-ended measurement is referenced to CR3000 ground, any
difference in ground potential between the sensor and the CR3000 will result in a
measurement error. Differential measurements MUST be used when the input
ground is known to be at a different ground potential from CR3000 ground. See
the section Single-Ended Measurements — Details
(p. 385)
for more information.
Ground potential differences are a common problem when measuring full-bridge
sensors (strain gages, pressure transducers, etc), and when measuring
thermocouples in soil.
7.3.3.1 Soil Temperature Thermocouple
If the measuring junction of a thermocouple is not insulated when in soil or water,
and the potential of earth ground is, for example, 1 mV greater at the sensor than
at the point where the CR3000 is grounded, the measured voltage is 1 mV greater
than the thermocouple output. With a copper-constantan thermocouple, 1 mV
equates to approximately 25 °C measurement error.
7.3.3.2 External Signal Conditioner
External instruments with integrated signal conditioners, such as an infrared gas
analyzer (IRGA), are frequently used to make measurements and send analog
information to the CR3000. These instruments are often powered by the same
Vac-line source as the CR3000. Despite being tied to the same ground,
differences in current drain and lead resistance result in different ground
Summary of Contents for CR3000 Micrologger
Page 2: ......
Page 3: ......
Page 4: ......
Page 6: ......
Page 30: ......
Page 34: ......
Page 36: ......
Page 96: ......
Page 485: ...Section 8 Operation 485 8 11 2 Data Display FIGURE 110 Keyboard and Display Displaying Data ...
Page 487: ...Section 8 Operation 487 FIGURE 112 CR1000KD Real Time Custom ...
Page 491: ...Section 8 Operation 491 FIGURE 116 Keyboard and Display File Edit ...
Page 496: ......
Page 502: ......
Page 564: ...Section 11 Glossary 564 FIGURE 126 Relationships of Accuracy Precision and Resolution ...
Page 566: ......
Page 594: ......
Page 598: ......
Page 600: ......
Page 602: ......
Page 624: ......
Page 642: ......
Page 643: ......