Section 7. Installation
180
the week, such as Monday or Friday. See CRBasic Editor Help topic
Function/EndFunction
7.6.4 Sending CRBasic Programs
The CR3000 requires that a CRBasic program file be sent to its memory to direct
measurement, processing, and data storage operations. The program file can
have the extension cr3 or .dld and can be compressed using the GZip algorithm
before sending it to the CR3000. Upon receipt of the file, the CR3000
automatically decompresses the file and uses it just as any other program file. See
Program and OS Compression Q and A
(p. 433)
for more information..
Options for sending a program include the following:
•
Program Send
(p. 550)
command in datalogger-support software
(p. 90)
•
Program send command in Device Configuration Utility (DevConfig
(p.
•
Campbell Scientific mass storage device
(p. 613)
or memory card
A good practice is to always retrieve data from the CR3000 before sending a
program; otherwise, data may be lost.
Note See File Management
(p. 456)
and the Campbell Scientific mass
storage device or memory card documentation available at
www.campbellsci.com.
7.6.4.1 Preserving Data at Program Send
You can send CRBasic programs to the CR3000 in multiple ways. Depending on
the way you choose, the CR3000 keeps or deletes data already stored in memory.
Regardless of the program-upload tool used, if any change occurs to the following
data table structures, data are erased when a new program is sent:
•
Data table name(s)
•
Data-output interval or offset
•
Number of fields per record
•
Number of bytes per field
•
Field type, size, name, or position
•
Number of records in table
The program sending command path options listed in table Program Send Options
That Reset Memory
(p. 181)
reset CR3000 memory and erase data. To keep data,
send programs using the File Control Send
(p. 539)
command in datalogger support
software
or the Compile > Compile, Save, Send command in CRBasic
Summary of Contents for CR3000 Micrologger
Page 2: ......
Page 3: ......
Page 4: ......
Page 6: ......
Page 30: ......
Page 34: ......
Page 36: ......
Page 96: ......
Page 485: ...Section 8 Operation 485 8 11 2 Data Display FIGURE 110 Keyboard and Display Displaying Data ...
Page 487: ...Section 8 Operation 487 FIGURE 112 CR1000KD Real Time Custom ...
Page 491: ...Section 8 Operation 491 FIGURE 116 Keyboard and Display File Edit ...
Page 496: ......
Page 502: ......
Page 564: ...Section 11 Glossary 564 FIGURE 126 Relationships of Accuracy Precision and Resolution ...
Page 566: ......
Page 594: ......
Page 598: ......
Page 600: ......
Page 602: ......
Page 624: ......
Page 642: ......
Page 643: ......