Section 7. Installation
303
PRTCalc() PRTType = 5
, α = 0.00375
1
Constant
Coefficient
h
-5.400
i
9.900
j
2.602
1
Honeywell Industrial Sensors, α = 0.00375 (Reference: Honeywell)
PRTCalc() PRTType = 6
, α = 0.003926
1
Constant
Coefficient
a
3.9848000E-03
d
-2.3480000E-06
e
1.8226630E-05
f
-1.1740000E-06
g
1.600
h
-2.400
i
8.800
j
2.502
1
Standard ITS-
90 SPRT, α = 0.003926 (Reference: Minco / Instrunet)
7.7.17.9 Self-Heating and Resolution
Programming the CR3000 to make a PRT measurement requires a judgment call.
To maximize measurement resolution, the excitation voltage must be maximized.
However, to minimize self-heating of the PRT element, excitation voltage must be
minimized. Keeping the voltage drop across the PRT to ≤2
5 mV addresses both
concerns since self-heating is normally less than 0.001°C in still air. To
maximize the measurement resolution, optimize the excitation voltage (Vx) such
that the voltage drop across the PRT spans, but does not exceed, the voltage input
range.
7.7.18 Serial I/O: Capturing Serial Data
The CR3000 communicates with smart sensors that deliver measurement data
through serial data protocols.
Read More See Comms and Data Retrieval
(p. 466)
for background on
CR3000 serial communications.
Summary of Contents for CR3000 Micrologger
Page 2: ......
Page 3: ......
Page 4: ......
Page 6: ......
Page 30: ......
Page 34: ......
Page 36: ......
Page 96: ......
Page 485: ...Section 8 Operation 485 8 11 2 Data Display FIGURE 110 Keyboard and Display Displaying Data ...
Page 487: ...Section 8 Operation 487 FIGURE 112 CR1000KD Real Time Custom ...
Page 491: ...Section 8 Operation 491 FIGURE 116 Keyboard and Display File Edit ...
Page 496: ......
Page 502: ......
Page 564: ...Section 11 Glossary 564 FIGURE 126 Relationships of Accuracy Precision and Resolution ...
Page 566: ......
Page 594: ......
Page 598: ......
Page 600: ......
Page 602: ......
Page 624: ......
Page 642: ......
Page 643: ......