Section 7. Installation
272
update the card sector, the first CR6 program compile with the card can take as
long as 30 minutes. After that, compile times will be normal.
Q:
Which memory card should I use?
A:
Campbell Scientific recommends and supports only the use of micro SD cards
obtained from Campbell Scientific. These cards are industrial-grade and have
passed Campbell Scientific hardware testing. Following are listed advantages
these cards have over less expensive commercial-grade cards:
•
less susceptible to failure and data loss
•
match the datalogger operating temperature range
•
faster read/write times
•
better vibration and shock resistance
•
longer life spans (more read/write cycles)
Q:
Can closed files be retrieved remotely?
A:
Yes. Closed files can be retrieved using the
Retrieve
function in the datalogger
support software
File Control
(p. 583)
utility, FTP, HTTP, or e-mail. Although open
files will appear in the CRD: drive directory, do not attempt to retrieve open files.
Doing so may corrupt the file and result in data loss. Smaller files typically
transmit more quickly and more reliably than large files.
Q:
Can data be accessed?
A:
Yes. Data in the open or most recent file can be collected using the
Collect
or
Custom Collect
utilities in
LoggerNet
,
PC400
, or
RTDAQ
. Data can also be
viewed using datalogger support software or accessed through the datalogger
using data table access syntax such as
TableName.FieldName
(see
CRBasic
Editor Help
). Once a file is closed, data can be accessed only by first retrieving
the file, as discussed previously, and processing the file using
CardConvert
software.
Q:
What happens when a card is inserted?
A:
When a card is inserted, whether it is a new card or the previously used card, a
new file is always created.
Q:
What does a power cycle or program restart do?
A:
Each time the program starts, whether by user control, power cycle, or a
watchdog,
TableFile()
with
Option 64
will create a new file.
Summary of Contents for CR6 Series
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 36: ......
Page 38: ......
Page 76: ...Section 5 Overview 76 FIGURE 20 Half Bridge Wiring Example Wind Vane Potentiometer ...
Page 80: ...Section 5 Overview 80 FIGURE 23 Pulse Input Wiring Example Anemometer ...
Page 136: ......
Page 454: ...Section 8 Operation 454 FIGURE 104 Narrow Sweep High Noise ...
Page 459: ...Section 8 Operation 459 FIGURE 106 Vibrating Wire Sensor Calibration Report ...
Page 535: ...Section 8 Operation 535 8 11 2 Data Display FIGURE 121 CR1000KD Displaying Data ...
Page 537: ...Section 8 Operation 537 FIGURE 123 CR1000KD Real Time Custom ...
Page 538: ...Section 8 Operation 538 8 11 2 3 Final Storage Data FIGURE 124 CR1000KD Final Storage Data ...
Page 539: ...Section 8 Operation 539 8 11 3 Run Stop Program FIGURE 125 CR1000KD Run Stop Program ...
Page 541: ...Section 8 Operation 541 FIGURE 127 CR1000KD File Edit ...
Page 546: ......
Page 552: ......
Page 610: ...Section 11 Glossary 610 FIGURE 137 Relationships of Accuracy Precision and Resolution ...
Page 612: ......
Page 648: ......
Page 650: ......
Page 688: ......
Page 689: ......