Section 7. Installation
300
FIGURE 67: Strain Gage Shunt
Calibration Finish
7.7.12.6.4 FieldCalStrain() Quarter-Bridge Zero
Continuing from
FieldCalStrain() Quarter-Bridge Shunt Example
(p. 299),
keep the
249 kΩ resistor in place to simulate a strain. Using the C
R1000KD
Keyboard/Display or software numeric monitor, change the value in variable
Zero_Mode
to
1
to start the zero calibration as shown in figure
Zero Procedure
Start
(p. 300).
When
Zero_Mode
increments to
6
, zero calibration is complete as
shown in figure
Zero Procedure Finish
(p. 300).
FIGURE 68: Zero Procedure Start
FIGURE 69: Zero Procedure Finish
Summary of Contents for CR6 Series
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 36: ......
Page 38: ......
Page 76: ...Section 5 Overview 76 FIGURE 20 Half Bridge Wiring Example Wind Vane Potentiometer ...
Page 80: ...Section 5 Overview 80 FIGURE 23 Pulse Input Wiring Example Anemometer ...
Page 136: ......
Page 454: ...Section 8 Operation 454 FIGURE 104 Narrow Sweep High Noise ...
Page 459: ...Section 8 Operation 459 FIGURE 106 Vibrating Wire Sensor Calibration Report ...
Page 535: ...Section 8 Operation 535 8 11 2 Data Display FIGURE 121 CR1000KD Displaying Data ...
Page 537: ...Section 8 Operation 537 FIGURE 123 CR1000KD Real Time Custom ...
Page 538: ...Section 8 Operation 538 8 11 2 3 Final Storage Data FIGURE 124 CR1000KD Final Storage Data ...
Page 539: ...Section 8 Operation 539 8 11 3 Run Stop Program FIGURE 125 CR1000KD Run Stop Program ...
Page 541: ...Section 8 Operation 541 FIGURE 127 CR1000KD File Edit ...
Page 546: ......
Page 552: ......
Page 610: ...Section 11 Glossary 610 FIGURE 137 Relationships of Accuracy Precision and Resolution ...
Page 612: ......
Page 648: ......
Page 650: ......
Page 688: ......
Page 689: ......