Section 7. Installation
308
'Excite - delay 1 second - differential measurement:
ExciteV
(U12,2500,0)
'<<<<Note: Delay = 0
Delay
(0,1000,mSec)
VoltDiff
(VoltageDIFF,1,mV5000,U3,True,0,15000,1.0,0)
'Write data to final-data memory
CallTable
Voltage
NextScan
EndProg
7.7.15 Serial I/O: SDI-12 Sensor Support — Details
Related Topics:
•
SDI-12 Sensor Support — Overview
(p. 83)
•
SDI-12 Sensor Support — Details
(p. 469)
•
Serial I/O: SDI-12 Sensor Support — Programming Resource
(p. 308)
See the table
CR6 Terminal Definitions
(p. 62)
for
U
and
C
terminal assignments for
SDI-12 input. Multiple SDI-12 sensors can be connected to each configured
terminal. If multiple sensors are wired to a single terminal, each sensor must have
a unique address. SDI-12 standard v 1.3 sensors accept addresses
0
through
9
,
a
through
z
, and
A
through
Z
. For a CRBasic programming example demonstrating
the changing of an SDI-12 address on the fly, see Campbell Scientific publication
PS200/CH200 12 V Charging Regulators
, which is available at
www.campbellsci.com
.
The CR6 supports SDI-12 communication through two modes — transparent
mode and programmed mode.
•
Transparent mode facilitates sensor setup and troubleshooting. It allows
commands to be manually issued and the full sensor response viewed.
Transparent mode does not record data.
•
Programmed mode automates much of the SDI-12 protocol and provides
for data recording.
7.7.15.1 SDI-12 Transparent Mode
System operators can manually interrogate and enter settings in probes using
transparent mode. Transparent mode is useful in troubleshooting SDI-12 systems
because it allows direct communication with probes.
Transparent mode may need to wait for commands issued by the programmed
mode to finish before sending responses. While in transparent mode, CR6
programs may not execute. CR6 security may need to be unlocked before
transparent mode can be activated.
Transparent mode is entered while the PC is in comms with the CR6 through a
terminal emulator program. It is easily accessed through a terminal emulator.
Campbell Scientific DevConfig program has a terminal utility, as to other
datalogger support software
(p. 97).
Keyboard displays cannot be used.
Summary of Contents for CR6 Series
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 36: ......
Page 38: ......
Page 76: ...Section 5 Overview 76 FIGURE 20 Half Bridge Wiring Example Wind Vane Potentiometer ...
Page 80: ...Section 5 Overview 80 FIGURE 23 Pulse Input Wiring Example Anemometer ...
Page 136: ......
Page 454: ...Section 8 Operation 454 FIGURE 104 Narrow Sweep High Noise ...
Page 459: ...Section 8 Operation 459 FIGURE 106 Vibrating Wire Sensor Calibration Report ...
Page 535: ...Section 8 Operation 535 8 11 2 Data Display FIGURE 121 CR1000KD Displaying Data ...
Page 537: ...Section 8 Operation 537 FIGURE 123 CR1000KD Real Time Custom ...
Page 538: ...Section 8 Operation 538 8 11 2 3 Final Storage Data FIGURE 124 CR1000KD Final Storage Data ...
Page 539: ...Section 8 Operation 539 8 11 3 Run Stop Program FIGURE 125 CR1000KD Run Stop Program ...
Page 541: ...Section 8 Operation 541 FIGURE 127 CR1000KD File Edit ...
Page 546: ......
Page 552: ......
Page 610: ...Section 11 Glossary 610 FIGURE 137 Relationships of Accuracy Precision and Resolution ...
Page 612: ......
Page 648: ......
Page 650: ......
Page 688: ......
Page 689: ......