Section 5. Overview
67
•
Continuous Analog Output (CAO) — available by adding a peripheral
analog output device available from Campbell Scientific. Refer to
Analog-Output Modules — List
(p. 477)
for information on available
expansion modules.
•
Switched Current Excitation — any
U
terminal configured for current
excitation with return to
terminal. These terminals are regularly
used with resistive-bridge measurements.
5.1.1.3 Power Terminals
5.1.1.3.1 Power In Terminals
The
– BAT +– CHG +
connector is the connection point for external power
supply components.
5.1.1.3.2 Power Out Terminals
Note
Refer to
Switched-Voltage Output — Details
(p. 473)
for more
information about using the CR6 as a power supply for sensors and
peripheral devices.
The CR6 can be used as a power source for sensors and peripherals. The
following voltages are available:
•
12V
terminals: unregulated nominal 12 Vdc. This supply closely tracks
the primary CR6 supply voltage, so it may rise above or drop below the
power requirement of the sensor or peripheral. Precautions should be
taken to prevent damage to sensors or peripherals from over- or
under-voltage conditions, and to minimize the error associated with the
measurement of underpowered sensors. See
Power Supplies —
Overview
•
U
and
C
terminals configured for power out — regulated ±2500 mV
•
U
terminals configured for power out — 3.3 or 5 Vdc
•
C
terminals configured for power out — 3.3 or 5 Vdc
5.1.1.4 Communication Ports — Overview
Related Topics:
•
Communication Ports — Overview
(p. 67)
•
Data Retrieval and Comms — Overview
(p. 85)
•
CPI Port and CDM Devices — Overview
(p. 70)
•
PakBus — Overview
(p. 87)
•
RS-232 and TTL
(p. 466)
Summary of Contents for CR6 Series
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 36: ......
Page 38: ......
Page 76: ...Section 5 Overview 76 FIGURE 20 Half Bridge Wiring Example Wind Vane Potentiometer ...
Page 80: ...Section 5 Overview 80 FIGURE 23 Pulse Input Wiring Example Anemometer ...
Page 136: ......
Page 454: ...Section 8 Operation 454 FIGURE 104 Narrow Sweep High Noise ...
Page 459: ...Section 8 Operation 459 FIGURE 106 Vibrating Wire Sensor Calibration Report ...
Page 535: ...Section 8 Operation 535 8 11 2 Data Display FIGURE 121 CR1000KD Displaying Data ...
Page 537: ...Section 8 Operation 537 FIGURE 123 CR1000KD Real Time Custom ...
Page 538: ...Section 8 Operation 538 8 11 2 3 Final Storage Data FIGURE 124 CR1000KD Final Storage Data ...
Page 539: ...Section 8 Operation 539 8 11 3 Run Stop Program FIGURE 125 CR1000KD Run Stop Program ...
Page 541: ...Section 8 Operation 541 FIGURE 127 CR1000KD File Edit ...
Page 546: ......
Page 552: ......
Page 610: ...Section 11 Glossary 610 FIGURE 137 Relationships of Accuracy Precision and Resolution ...
Page 612: ......
Page 648: ......
Page 650: ......
Page 688: ......
Page 689: ......