Section 7. Installation
192
7.6.3.3.2 Dimensioning Numeric Variables
Some applications require multi-dimension arrays. Array dimensions are
analogous to spatial dimensions (distance, area, and volume). A single-dimension
array, declared as,
Public VariableName(x)
with (x) being the index, denotes
x
number of variables as a series.
A two-dimensional array, declared as,
Public VariableName(x,y)
with (x,y) being the indices, denotes (
x
•
y
) number of variables in a square x-by-y
matrix.
Three-dimensional arrays, declared as
Public VariableName (x,y,z)
with (x,y,z) being the indices, have (x • y • z) number of variables in a cubic
x-by-y-by-z matrix. Dimensions greater than three are not permitted by
CRBasic.
When using variables in place of integers as dimension indices (see CRBasic
example
Using Variable Array Dimension Indices
(p. 192))
, declaring the indices
As
Long
variables is recommended. Doing so allows for more efficient use of CR6
resources.
Using Variable Array Dimension Indices
'This program example demonstrates the use of dimension indices in arrays. The variable
'VariableName is declared with three dimensions with 4 in each index. This indicates the
'array has means it has 64 elements. Element 24 is loaded with the value 2.718.
'
Dim
aaa
As Long
Dim
bbb
As Long
Dim
ccc
As Long
Public
VariableName(4,4,4)
As Float
BeginProg
Scan
(1,sec,0,0)
aaa = 3
bbb = 2
ccc = 4
VariableName(aaa,bbb,ccc) = 2.718
NextScan
EndProg
7.6.3.3.3 Dimensioning String Variables
Strings can be declared to a maximum of two dimensions. The third "dimension"
is used for accessing characters within a string. See
String Operations
(p. 379).
Summary of Contents for CR6 Series
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 36: ......
Page 38: ......
Page 76: ...Section 5 Overview 76 FIGURE 20 Half Bridge Wiring Example Wind Vane Potentiometer ...
Page 80: ...Section 5 Overview 80 FIGURE 23 Pulse Input Wiring Example Anemometer ...
Page 136: ......
Page 454: ...Section 8 Operation 454 FIGURE 104 Narrow Sweep High Noise ...
Page 459: ...Section 8 Operation 459 FIGURE 106 Vibrating Wire Sensor Calibration Report ...
Page 535: ...Section 8 Operation 535 8 11 2 Data Display FIGURE 121 CR1000KD Displaying Data ...
Page 537: ...Section 8 Operation 537 FIGURE 123 CR1000KD Real Time Custom ...
Page 538: ...Section 8 Operation 538 8 11 2 3 Final Storage Data FIGURE 124 CR1000KD Final Storage Data ...
Page 539: ...Section 8 Operation 539 8 11 3 Run Stop Program FIGURE 125 CR1000KD Run Stop Program ...
Page 541: ...Section 8 Operation 541 FIGURE 127 CR1000KD File Edit ...
Page 546: ......
Page 552: ......
Page 610: ...Section 11 Glossary 610 FIGURE 137 Relationships of Accuracy Precision and Resolution ...
Page 612: ......
Page 648: ......
Page 650: ......
Page 688: ......
Page 689: ......