Section 7. Installation
285
terminals
U1
and
U11
. The following variables are preset by the program:
SimulatedRHSignal
=
100
,
KnownRH
=
0
.
3. To start the 'calibration', set variable
CalMode
=
1
. When
CalMode
increments to
6
, zero calibration is complete. Calibrated
RHOffset
will equal
-5
% at this stage of this example.
4. To continue this example and simulate a zero-drift condition, set variable
SimulatedRHSignal
=
105
.
5. To simulate conditions for a 30-day-service calibration, again with desiccated
chamber conditions, keep variable
KnownRH
=
0.0
. Set variable
CalMode
=
1
to start calibration. When
CalMode
increments to
6
, simulated
30-day-service zero calibration is complete. Calibrated
RHOffset
will equal
-5.2
%.
FieldCal()
Zero
'This program example demonstrates the use of FieldCal() in calculating and applying a zero
'calibration. A zero calibration measures the signal magnitude of a sensor in a known zero
'condition and calculates the negative magnitude to use as an offset in subsequent
'measurements. It does not affect the multiplier.
'
'This program demonstrates the zero calibration with the following procedure:
' -- Simulate a signal from a relative-humidity sensor.
' -- Measure the 'sensor' signal.
' -- Calculate and apply a zero calibration.
'You can set up the simulation by loading this program into the CR6 and interconnecting
'the following terminals with a jumper wire to simulate the relative-humidity sensor signal
'as follows:
'
U11
---
U
1
'For the simulation, the initial 'sensor' signal is set automatically. Start the zero routine
'by setting variable CalMode = 1. When CalMode = 6 (will occur automatically after 10
'measurements), the routine is complete. Note the new value in variable RHOffset. Now
'enter the following millivolt value as the simulated sensor signal and note how the new
'offset is added to the measurement:
' SimulatedRHSignal = 1000
'NOTE: This program places a .cal file on the CPU: drive of the CR6. The .cal file must
'be erased to reset the demonstration.
'DECLARE SIMULATED SIGNAL VARIABLE AND SET INITIAL MILLIVOLT SIGNAL MAGNITUDE
Public
SimulatedRHSignal =
100
'DECLARE CALIBRATION STANDARD VARIABLE AND SET PERCENT RH MAGNITUDE
Public
KnownRH = 0
'DECLARE MEASUREMENT RESULT VARIABLE.
Public
RH
'DECLARE OFFSET RESULT VARIABLE
Public
RHOffset
Summary of Contents for CR6 Series
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 36: ......
Page 38: ......
Page 76: ...Section 5 Overview 76 FIGURE 20 Half Bridge Wiring Example Wind Vane Potentiometer ...
Page 80: ...Section 5 Overview 80 FIGURE 23 Pulse Input Wiring Example Anemometer ...
Page 136: ......
Page 454: ...Section 8 Operation 454 FIGURE 104 Narrow Sweep High Noise ...
Page 459: ...Section 8 Operation 459 FIGURE 106 Vibrating Wire Sensor Calibration Report ...
Page 535: ...Section 8 Operation 535 8 11 2 Data Display FIGURE 121 CR1000KD Displaying Data ...
Page 537: ...Section 8 Operation 537 FIGURE 123 CR1000KD Real Time Custom ...
Page 538: ...Section 8 Operation 538 8 11 2 3 Final Storage Data FIGURE 124 CR1000KD Final Storage Data ...
Page 539: ...Section 8 Operation 539 8 11 3 Run Stop Program FIGURE 125 CR1000KD Run Stop Program ...
Page 541: ...Section 8 Operation 541 FIGURE 127 CR1000KD File Edit ...
Page 546: ......
Page 552: ......
Page 610: ...Section 11 Glossary 610 FIGURE 137 Relationships of Accuracy Precision and Resolution ...
Page 612: ......
Page 648: ......
Page 650: ......
Page 688: ......
Page 689: ......