Section 8. Operation
439
Note
Peripheral devices are available from Campbell Scientific to expand
the number of pulse input channels measured by the CR6. See
Measurement and Control Peripherals — List
(p. 652).
The figure
Pulse Sensor Output Signal Types
(p. 79)
illustrates pulse signal types
measurable by the CR6:
•
low-level ac
•
high-frequency
•
switch closure
The figure
Switch Closure Pulse Sensor
(p. 440)
illustrates the basic internal circuit
and the external connections of a switch closure pulse sensor. The table Pulse
Measurements: Terminals and Programming
summarizes available measurements,
terminals available for those measurements, and the CRBasic instructions used.
The number of terminals configurable for pulse input is determined from the table
CR6 Terminal Definitions
(p. 62).
For example, suppose you need to measure the seven pulse inputs listed in the
following table. How many
U
and
C
terminals are needed, and what CRBasic
instructions are used? Measurement requirements are listed to the right of the
table, solutions to the left.
Pulse Measurement Application Examples
Measurement Requirements
Solution
Pulse Sensor Type
Data
Terminal
Instruction
PConfig
Argument
POption
Argument
low-level ac
count
Even
U
terminal
PulseCount()
5
0
low-level ac
running average
Even
U
terminal
PulseCount()
5
>1
square-wave high
frequency
counts
U
or
C
terminal
PulseCount()
3 or 4
0
square-wave high
frequency
frequency
U
or
C
terminal
PulseCount()
3 or 4
1
switch closure
counts
U
or
C
terminal
PulseCount()
1 or 2
0
switch closure
frequency
U
or
C
terminal
PulseCount()
1 or 2
1
square-wave
high-frequency
count of edges
U
or
C
terminal
TimerInput()
n/a
n/a
Summary of Contents for CR6 Series
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 36: ......
Page 38: ......
Page 76: ...Section 5 Overview 76 FIGURE 20 Half Bridge Wiring Example Wind Vane Potentiometer ...
Page 80: ...Section 5 Overview 80 FIGURE 23 Pulse Input Wiring Example Anemometer ...
Page 136: ......
Page 454: ...Section 8 Operation 454 FIGURE 104 Narrow Sweep High Noise ...
Page 459: ...Section 8 Operation 459 FIGURE 106 Vibrating Wire Sensor Calibration Report ...
Page 535: ...Section 8 Operation 535 8 11 2 Data Display FIGURE 121 CR1000KD Displaying Data ...
Page 537: ...Section 8 Operation 537 FIGURE 123 CR1000KD Real Time Custom ...
Page 538: ...Section 8 Operation 538 8 11 2 3 Final Storage Data FIGURE 124 CR1000KD Final Storage Data ...
Page 539: ...Section 8 Operation 539 8 11 3 Run Stop Program FIGURE 125 CR1000KD Run Stop Program ...
Page 541: ...Section 8 Operation 541 FIGURE 127 CR1000KD File Edit ...
Page 546: ......
Page 552: ......
Page 610: ...Section 11 Glossary 610 FIGURE 137 Relationships of Accuracy Precision and Resolution ...
Page 612: ......
Page 648: ......
Page 650: ......
Page 688: ......
Page 689: ......