Appendix A. Info Tables and Settings
626
ChargeState
String
Y
•
Status
table field: ≈16
State of the
CHG
terminals. Responses include
Regulator Fault
,
No Charge
,
Current
Limit
,
Float Charge
,
Low Charge Input
. Updates when auto self-calibration executes
(once per minute).
CommActive()
Discontinued in OS 28 of CR800, CR1000, CR3000. Never in CR6. Function is replaced
by CRBasic instruction
ComPortIsActive()
.
CommConfig()
Discontinued
Comms
MemAlloc
Numeric
•
Settings Editor:
Advanced | Communication Allocation
Replaces
PakBusNodes
. Specifies the amount of memory that the CR6 allocates for maintaining
PakBus routing information. Represents roughly the maximum number of PakBus nodes that the
CR6 tracks in its routing tables. Default =
50
, which is normally enough. Can probably be reduced in
small networks to free memory.
Comms
MemFree
Numeric Y
•
Status
table field: ≈29
Buffers used in all communications, except with a keyboard dispaly, including routing and
neighbors (each route or neighbor requires 1 buffer). Updated when status is queried.
A
CompileResults
String
Y
•
Station Status field:
Results for Last Program Compiled
•
Status
table field: ≈18
Contains error messages generated at compilation or during runtime. Updated after compile.
Also appended to at run time for run time errors such as variable out of bounds.
ConfigComC1
UINT1
•
Settings Editor:
Com Ports Settings | Control COMC1 | Configuration
Setup of
ComC1
terminals
ConfigComC3
UINT1
•
Settings Editor:
Com Ports Settings | Control COMC3 | Configuration
Setup of
ComC3
terminals
CPUDriveFree
Numeric Y
•
Keyboard:
Settings (Datalogger)
Bytes remaining on the CPU: drive.
CSIO1net
Enable
Numeric
•
Settings Editor:
CS I/O IP | Enabled #2
CSIO2net
Enable
Numeric
•
Settings Editor:
CS I/O IP | Enabled (#1)
CSIOInfo
String
•
Settings Editor:
CS I/O | {info box}
2
Order and definitions of auto self-calibration array elements:
(1) 5000 mV range
(2) 1000 mV range
(3) 200 mV range
Summary of Contents for CR6 Series
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 36: ......
Page 38: ......
Page 76: ...Section 5 Overview 76 FIGURE 20 Half Bridge Wiring Example Wind Vane Potentiometer ...
Page 80: ...Section 5 Overview 80 FIGURE 23 Pulse Input Wiring Example Anemometer ...
Page 136: ......
Page 454: ...Section 8 Operation 454 FIGURE 104 Narrow Sweep High Noise ...
Page 459: ...Section 8 Operation 459 FIGURE 106 Vibrating Wire Sensor Calibration Report ...
Page 535: ...Section 8 Operation 535 8 11 2 Data Display FIGURE 121 CR1000KD Displaying Data ...
Page 537: ...Section 8 Operation 537 FIGURE 123 CR1000KD Real Time Custom ...
Page 538: ...Section 8 Operation 538 8 11 2 3 Final Storage Data FIGURE 124 CR1000KD Final Storage Data ...
Page 539: ...Section 8 Operation 539 8 11 3 Run Stop Program FIGURE 125 CR1000KD Run Stop Program ...
Page 541: ...Section 8 Operation 541 FIGURE 127 CR1000KD File Edit ...
Page 546: ......
Page 552: ......
Page 610: ...Section 11 Glossary 610 FIGURE 137 Relationships of Accuracy Precision and Resolution ...
Page 612: ......
Page 648: ......
Page 650: ......
Page 688: ......
Page 689: ......