Section 7. Installation
260
PRT Measurement Circuit Overview
Configuration
Features
Note
•
Voltage Excitation
Four-wire half-bridge (p. 262)
•
High accuracy over long leads
•
More input terminals: four per sensor
•
Slower: four differential sub
measurements per measurement
Best configuration
Three-wire half-bridge (p. 266)
•
Good accuracy over long leads.
•
Fewer input terminals: two per sensor
•
Faster: two single-ended sub
measurements per measurement
Costs less to build
Four-wire full-bridge (p. 270)
•
High resolution response to change
•
More complicated to build
•
Two input terminals per sensor
•
Two differential sub measurements
per measurement
•
Best over short leads.
•
Best resolution since the
bridge balances at the
temperature-range midpoint.
7.7.16.2 General Procedure (PRT)
Following is a general procedure for using a PRT:
1.
Build circuit.
2.
Wire circuit to the CR800.
3.
Calculate excitation voltage.
4.
Calibrate PRT.
5.
Measure PRT and convert output to temperature.
Several procedures follow that step you through use of common resistive-bridge
configurations to measure a 100 Ω PRT (a.k.a, PT100). Use the following data to
help you understand the examples:
Procedure Data
•
Units u
sed in examples: mV (millivolts), mA (milliamperes), and mΩ
(milliohms)
•
RTD type for examples: 100 Ω PRT (a.k.a, PT100), α = 0.00385
•
Temperature measurement range for examples: –40 to 60 °C
•
General forms of Callander-Van Dusen equations using CRBasic
notation:
o
T = g * K^4 + h * K^3 + i * K^2 + j * K (temperatures < 0°C)
o
T = (SQRT(d * (RS/RS0) + e)
-
a) / f (temperature ≥ 0°C)
Summary of Contents for CR800 Series
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 34: ......
Page 54: ......
Page 92: ......
Page 310: ......
Page 446: ...Section 8 Operation 446 8 11 2 Data Display FIGURE 100 CR1000KD Displaying Data ...
Page 448: ...Section 8 Operation 448 FIGURE 102 CR1000KD Real Time Custom ...
Page 449: ...Section 8 Operation 449 8 11 2 3 Final Storage Data FIGURE 103 CR1000KD Final Storage Data ...
Page 450: ...Section 8 Operation 450 8 11 3 Run Stop Program FIGURE 104 CR1000KD Run Stop Program ...
Page 452: ...Section 8 Operation 452 FIGURE 106 CR1000KD File Edit ...
Page 456: ......
Page 462: ......
Page 523: ...Section 11 Glossary 523 FIGURE 116 Relationships of Accuracy Precision and Resolution ...
Page 524: ......
Page 526: ......
Page 556: ......
Page 558: ......
Page 560: ......
Page 597: ......