Section 8. Operation
415
Record Element 1 – Timestamp
Data without timestamps are usually meaningless. Nevertheless, the
TableFile()
instruction optionally includes timestamps in some formats.
Record Element 2 – Record Number
Record numbers are optionally provided in some formats as a means to
ensure data integrity and provide an up-count data field for graphing
operations. The maximum record number is &hffffffff (a 32-bit number),
then the record number sequence restarts at zero. The CR800 reports back to
the datalogger support software 31 bits, or a maximum of &h7fffffff, then it
restarts at 0. For example, if the record number increments once a second,
restart at zero will occur about once every 68 years (yes, years).
8.8.3 Resetting the CR800
A reset is referred to as a "memory reset." Be sure to backup the current CR800
configuration before a reset in case you need to revert to the old settings.
The following features are available for complete or selective reset of CR800
memory:
•
Full memory reset
•
Program send reset
•
Manual data-table reset
•
Formatting memory drives
8.8.3.1 Full Memory Reset
Full memory reset occurs when an operating system is sent to the CR800 using
DevConfig
or when entering
98765
in the
Status
table field
FullMemReset
(p. 541).
A full memory reset does the following:
•
Clears and formats CPU: drive (all program files erased)
•
Clears SRAM data tables
•
Clears
Status
-table elements
•
Restores settings to default
•
Initializes system variables
•
Clears communication memory
Summary of Contents for CR800 Series
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 34: ......
Page 54: ......
Page 92: ......
Page 310: ......
Page 446: ...Section 8 Operation 446 8 11 2 Data Display FIGURE 100 CR1000KD Displaying Data ...
Page 448: ...Section 8 Operation 448 FIGURE 102 CR1000KD Real Time Custom ...
Page 449: ...Section 8 Operation 449 8 11 2 3 Final Storage Data FIGURE 103 CR1000KD Final Storage Data ...
Page 450: ...Section 8 Operation 450 8 11 3 Run Stop Program FIGURE 104 CR1000KD Run Stop Program ...
Page 452: ...Section 8 Operation 452 FIGURE 106 CR1000KD File Edit ...
Page 456: ......
Page 462: ......
Page 523: ...Section 11 Glossary 523 FIGURE 116 Relationships of Accuracy Precision and Resolution ...
Page 524: ......
Page 526: ......
Page 556: ......
Page 558: ......
Page 560: ......
Page 597: ......