Section 8. Operation
345
For a complete treatment of current-loop sensors (4 to 20 mA, for example),
please consult the following publications available at
www.campbellsci.com/app-
notes
:
•
Current Output Transducers Measured with Campbell Scientific
Dataloggers (2MI-B)
•
CURS100 100 Ohm Current Shunt Terminal Input Module
8.1.2.7 Voltage Measurements — Details
Related Topics:
• Voltage Measurements — Specifications
•
Voltage Measurements — Overview
(p. 65)
•
Voltage Measurements — Details
(p. 345)
8.1.2.7.1 Voltage Measurement Limitations
Caution
Sustained voltages in excess of
±
8.6 V applied to terminals
configured for analog input can temporarily corrupt all analog
measurements.
Warning
Sustained voltages in excess of
±
16 V applied to terminals
configured for analog input will damage CR800 circuitry.
Voltage Ranges
Related Topics:
• Voltage Measurements — Specifications
•
Voltage Measurements — Overview
(p. 65)
•
Voltage Measurements — Details
(p. 345)
In general, use the smallest fixed-input range that accommodates the full-scale
output of the sensor. This results in the best measurement accuracy and resolution.
The CR6 has fixed input ranges for voltage measurements and an auto-range to
automatically determine the appropriate input voltage range for a given
measurement. The table
Analog Voltage Input Ranges and Options
(p. 346)
lists
these input ranges and codes.
An approximate 9% range overhead exists on fixed input voltage ranges. In
other words, over-range on the
±
2500 mV input range occurs at approximately
2725 mV and –2725 mV. The CR800 indicates a measurement over-range by
returning a
NAN
(not a number) for the measurement.
Automatic Range Finding
For signals that do not fluctuate too rapidly, range argument
AutoRange
allows
the CR800 to automatically choose the voltage range.
AutoRange
makes two
Summary of Contents for CR800 Series
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 34: ......
Page 54: ......
Page 92: ......
Page 310: ......
Page 446: ...Section 8 Operation 446 8 11 2 Data Display FIGURE 100 CR1000KD Displaying Data ...
Page 448: ...Section 8 Operation 448 FIGURE 102 CR1000KD Real Time Custom ...
Page 449: ...Section 8 Operation 449 8 11 2 3 Final Storage Data FIGURE 103 CR1000KD Final Storage Data ...
Page 450: ...Section 8 Operation 450 8 11 3 Run Stop Program FIGURE 104 CR1000KD Run Stop Program ...
Page 452: ...Section 8 Operation 452 FIGURE 106 CR1000KD File Edit ...
Page 456: ......
Page 462: ......
Page 523: ...Section 11 Glossary 523 FIGURE 116 Relationships of Accuracy Precision and Resolution ...
Page 524: ......
Page 526: ......
Page 556: ......
Page 558: ......
Page 560: ......
Page 597: ......