Section 8. Operation
389
•
PLC Control Modules — Overview
(p. 394)
•
PLC Control Modules — Lists
(p. 565)
The CR800 wiring panel is a convenient power distribution device for powering
sensors and peripherals that require a 5 Vdc, or 12 Vdc source. It has one
continuous 12 Vdc terminal (
12V
), one program-controlled, switched, 12 Vdc
terminal (
SW12
), and one continuous 5 Vdc terminal (
5V
).
SW12
,
12V
, and
5V
terminals limit current internally for protection against accidental short circuits.
Voltage on the
12V
and
SW12
terminals can vary widely and will fluctuate with
the dc supply used to power the CR800, so be careful to match the datalogger
power supply to the requirements of the sensors. The
5V
terminal is internally
regulated to within ±4%, which is good regulation as a power source, but typically
not adequate for bridge sensor excitation.
TABLE: Current Sourcing Limits
(p. 389)
lists the current limits of
12V
and
5V
terminals. Greatly reduced output
voltages on these terminals may occur if the current limits are exceeded. See
Terminals Configured for Control
(p. 392)
for more information.
Current Source and Sink Limits
Terminal
Limit
1
VX
or
EX
(voltage excitation)
2
±25 mA maximum
SW12
3
< 900 mA @ 20°C
< 630 mA @ 50°C
< 450 mA @ 70°C
< 360 mA @ 85°C
12V
+
SW12
(combined)
4
< 1.85 A @ 20°C
< 1.33 A @ 50°C
< 1.00 A @ 70°C
< 0.74 A @ 85°C
5V
+
CS I/O
(combined)
5
< 200 mA
1
Source
is positive amperage (+);
sink
is negative amperage (–).
2
Exceeding current limits will cause voltage output to become unstable. Voltage should stabilize
once current is again reduced to within stated limits.
3
A polyfuse is used to limit power. Result of overload is a voltage drop. To reset, disconnect and
allow circuit to cool.
4
Polyfuse protected. See footnote 3.
5
Current is limited by a current limiting circuit, which holds the current at the maximum by
dropping the voltage when the load is too great.
8.2.1 Switched-Voltage Excitation
Two switched, analog-output (excitation) terminals (
VX1
to
VX2
) operate under
program control to provide ±2500 mV dc excitation. Check the accuracy
Summary of Contents for CR800 Series
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 34: ......
Page 54: ......
Page 92: ......
Page 310: ......
Page 446: ...Section 8 Operation 446 8 11 2 Data Display FIGURE 100 CR1000KD Displaying Data ...
Page 448: ...Section 8 Operation 448 FIGURE 102 CR1000KD Real Time Custom ...
Page 449: ...Section 8 Operation 449 8 11 2 3 Final Storage Data FIGURE 103 CR1000KD Final Storage Data ...
Page 450: ...Section 8 Operation 450 8 11 3 Run Stop Program FIGURE 104 CR1000KD Run Stop Program ...
Page 452: ...Section 8 Operation 452 FIGURE 106 CR1000KD File Edit ...
Page 456: ......
Page 462: ......
Page 523: ...Section 11 Glossary 523 FIGURE 116 Relationships of Accuracy Precision and Resolution ...
Page 524: ......
Page 526: ......
Page 556: ......
Page 558: ......
Page 560: ......
Page 597: ......