7.6 Testing CRVW3 measurements
Once configured, the CRVW3 will restart and automatically begin measuring sensors at the
interval specified. The data is stored as each measurement is made.
Use
Device Configuration Utility
in the lab to confirm measurements are being made by the
CRVW3.
1. Select Logger Control tab. The Station Time should update once every second.
2. Select Data Monitor to view data being stored in the final storage and utility tables of the
device. Click on a table name in the left pane to see its latest stored record in the right
pane. The Status table shows general information about the CRVW3 and its operation. The
Public table shows information about specific variables in use by the current program
configuration. The VW_Data table is the main storage table. This is where a permanent
history of sensor readings is stored. The DataTableInfo table gives details about final
storage tables in use by the device. If calibration settings are used (baseline values), a
CalHist table will also appear that shows calibration values captured during the latest
calibration event.
CRVW3 3-Channel Vibrating-Wire Data Logger
25