2. Expected sensor address has been to match another sensor address already in use.
a. When readdressing temperature sensors, you must avoid giving multiple sensors the
same address. If this does occur, you will no longer be able to communicate with
these sensors. Use the
aA{!
command, where a is the affected address. This will
reset the affected sensors to their factory configured address value. For example, if
two sensors have address 2, sending
2A{!
will reset both sensors to the original
addresses.
CS225 Temperature String
16