4.1 Physical Set-up
Always power down the datalogger before installing or
removing the NL115 to/from the datalogger.
CAUTION
After powering down the datalogger, plug the NL115 into the datalogger
peripheral port (see Figure 4-1). Attach Ethernet cable to the 10 Base T port.
If using the 28033 surge protector, connect the other end of the Ethernet cable
to the 28033 and connect another Ethernet cable to the other end of the 28033.
Restore power to the datalogger. Insert formatted CF card. (For instructions
on formatting a CF card, see Appendix A.)
A CF card does not need to be present in order to use the
NL115’s TCP/IP functionality.
NOTE
FIGURE 4-1. NL115 attached to a CR1000
4.2 Communicating via Ethernet
4.2.1 Step 1 – Configure Datalogger
a.
Connect serial cable from PC COM port to datalogger RS-232 port.
b.
Open Campbell Scientific’s Device Configuration Utility. Select the
device type of the datalogger (CR1000 or CR3000), the appropriate Serial
Port and baud rate. Connect to the datalogger.
c.
Under the TCP/IP tab, input the IP Address, Subnet Mask and IP
gateway. These values should be provided by your network
administrator.