SC932A CS I/O to RS-232-DCE Interface 

4.3  Testing RAD Modem Communication 

The modem communication link is divided into the following three sections: 

1) RAD modem computer end, 2) cable from computer modem to data logger

modem, and 3) RAD modem data logger end. When unable to establish

communication with the data logger, test each of the three sections. See a blog

article at: 

www.campbellsci.com/blog/test-com-ports-short-haul-modems

.

Before proceeding through the testing procedures, a terminal emulator software 

program such as Campbell Scientific’s 

Terminal Emulator

 (included with 

LoggerNet

PC400

, and 

Device Configuration Utility

) must be used to 

communicate through the COM port of the computer. Once the emulator 

program is set up, testing can proceed as follows: 

1. Disconnect the four conductor cables from the SRM-6A RAD modem at

the computer end. Jumper the XMT + to RCV + and jumper the XMT – to

RCV –. This creates a transmit loop which allows any key pressed at the

computer keyboard to be seen on the screen. If the key pressed is not seen,

check the following: COM port configuration, 25-pin cable from the

computer to the modem and the RAD modem.

2. Reconnect the four conductor cables to the modem at the computer end

and disconnect the cable from the modem at the data logger end. Twist

together the XMT + wire and RCV + wire, twist together the XMT – wire

and the RCV – wire. Repeat the process of step 1 by pressing a key on the

computer keyboard. If the key pressed is not returned, then the cable from

the modem at the computer to the data logger modem is defective and will

need to be repaired or replaced.

3. If steps 1 and 2 pass, the modem at the data logger is suspect. Disconnect

the modem from the SC932A and bring the modem to the computer site.

Attach the modem to the computer, and repeat step 1 by jumpering the

terminals of the modem and pressing a key on the computer keyboard.

If the above tests pass and communication to the data logger still has not been 

established, perform tests 4, 5, and 6.  

4. A 12 V lead acid battery supply should not be discharged below 11.76 V.

If this occurs, the batteries will go into a deep discharge state and will

need to be replaced. Check the 12 V supply with a volt meter.

5. On the wiring panel of most Campbell Scientific data loggers there is a

terminal marked 5 V. Check the 5 V supply with a volt meter. This 5 V

supply should be within a tenth of a volt. If not, it would indicate a

problem.

6. To verify that the data logger and its serial I/O port are working, try to

access input memory locations using a laptop PC with the SC32B or the

CR10KD Keyboard Display.

If the data logger passes tests 4, 5, and 6, then the SC932A is suspect and will 

need to be repaired or replaced. 

Summary of Contents for SC932A

Page 1: ...SC932A CS I O to RS 232 DCE Interface Revision 12 2022 Copyright 1987 2022 Campbell Scientific CSL I D 483...

Page 2: ...under guarantee or not Please state the faults as clearly as possible and if the product is out of the guarantee period it should be accompanied by a purchase order Quotations for repairs can be give...

Page 3: ...cell phones and aerials may also not be applicable according to your locality Some brackets shields and enclosure options including wiring are not sold as standard items in the European market in some...

Page 4: ...beginning work Wear a hardhat and eye protection and take other appropriate safety precautions while working on or around tripods and towers Do not climb tripods or towers at any time and prohibit cl...

Page 5: ...ions 1 General Description 1 2 Specifications 2 3 Installation 3 4 RAD Modem Application 3 4 1 RAD Modem Two Way 4 4 2 RAD Modem Wiring and Grounding 4 4 3 Testing RAD Modem Communication 6 Figures 1...

Page 6: ...the 5 V supply on pin 1 of the data logger s CS I O port The SC932A will use the 5 V supply to power the RS 232 modem if needed Two way interactive communication The SC932A is frequently used with a s...

Page 7: ...Ground 6 In DSR Data Set Ready No Connection 7 Out RTS Request to Send Modem Enable 8 In CTS Clear to Send No Connection 9 In Ring Rings Data Logger CS I O 9 Pin Male Connector Pin out Pin No I O Nam...

Page 8: ...oper transient protection should be installed to protect the computer and data logger in areas where damage due to lightning is possible If this is a RAD modem application see Section 4 2 RAD Modem Wi...

Page 9: ...ollows 1 Set the DCE DTE switch on the back of the RAD modem connected to the SC932A to DCE For a RAD modem connected to a PC set the DCE DTE switch to DCE For a RAD modem connected to a serial printe...

Page 10: ...stomer needs to transmit data across longer or smaller gauge wires or at higher speeds than can be done with the RAD modem powered by the SC932A RAD does sell a 9 volt power supply that will boost the...

Page 11: ...em at the data logger end Twist together the XMT wire and RCV wire twist together the XMT wire and the RCV wire Repeat the process of step 1 by pressing a key on the computer keyboard If the key press...

Page 12: ...nfo campbellsci fr www campbellsci fr Germany Location Phone Email Website Bremen Germany 49 0 421 460974 0 info campbellsci de www campbellsci de India Location Phone Email Website New Delhi DL India...

Reviews: