On the PPP tab select the Config/Port Used where the modem

is connected. This is the same as was selected on the Com Ports

Settings tab. Set Modem Dial String to ATH;AT\APPP.

Apply to save your changes.
Disconnect the Ethernet cable between the RV50(X) and

computer.

6. Set up LoggerNet

1. Select Add Root > IPPort.

2. Select PakBusPort
3. Add a data logger to the PakBusPort.
4. Select the IPPort in the Network Map. Enter the RV50(X)

IP address and port number. The IP address and port

number are input in the Internet IP Address field

separated by a colon. Preceding zeros are not entered

in the Internet IP Address (for example, 070.218.074.247

is entered as 70.218.74.247). The default port number is

6785.

5. For PakBus data loggers, leave the default settings for

the PakBusPort. PakBus Port Always Open should not be

checked. If used, enter the TCP Password.

6. For PakBus data loggers, select the data logger in the

Network Map and set the PakBus Address to match that

of the data logger (default address in the data logger is

1). If a PakBus Encryption Key was entered during data

logger setup, also enter it here. Click Apply to save the

changes.

7. Test the connection

Use the Connect screen to test the connection. Click on the

appropriate station and click Connect to initiate a call to the

data logger. The data logger must have 12 V power.

TIP:

The connection time is subject to many external factors. It

is often less than 30 seconds but could be up to 15 minutes.

Be patient.

If the connection is successful, the connectors at the bottom of

the screen will come together and clock information from the

data logger will be displayed in the Station Date/Time field.