7. Installation
If you are programming your data logger with
Short Cut
, skip
(p. 8) and
Short Cut
does this work for you. See
(p. 3), for a
Short Cut
tutorial.
This section discusses the following.
7.4 Installation in a radiation shield
7.1 Wiring
Campbell Scientific offers extension cables in lengths up to 10 m, which connect to the TempVue
20 SDI-12 M12 connector. Contact Campbell Scientific if a longer cable is required.
(p. 8) provides data logger connections. Connect the wires in the order shown in the
table.
Table 7-1: SDI-12 wire color, function, and data logger connection
Wire color
Wire function
Data loggerconnection
White
SDI-12 signal
C, SDI-12, or CR6 U terminal configured
for SDI-12
1
Brown
Power
12V
Black
Power ground
G
Clear
Shield
G
Grey
Aspen detect signal
G
Other colors
N/A
not used
2
1
U and C terminals are automatically configured by the measurement instruction.
2
Individually isolate the unused wires with electrical tape or wire caps.
TempVue 20 SDI-12 PT-100 Class A, Precision Air Temperature Sensor
8