8. Type SDI12 and press Enter.
9. At the Select SDI12 Port prompt, type the number corresponding to the control port where
the sensor is connected and press Enter. In this example the sensor is connected to C3. The
response Entering SDI12 Terminal indicates that the sensor is ready to accept SDI-12
commands.
10. To query the sensor for its current SDI-12 address, type ?! and press Enter. The sensor
responds with its SDI-12 address. If no characters are typed within 60 seconds, the mode is
exited. In that case, simply type SDI12 again, press Enter, and type the correct control port
number when prompted.
11. To change the SDI-12 address, type aAb!, where a is the current address from the previous
step and b is the new address. Press Enter. The sensor changes its address and responds
with the new address. In the following example, the sensor address is changed from 0 to B.
12. To exit SDI-12 transparent mode, click Close Terminal.
NOTE:
The transparent mode for the Granite-series, CR6, CR3000, CR800-series, CR300-series data
loggers is similar to that shown for the CR1000X.
TempVue 20 SDI-12 PT-100 Class A, Precision Air Temperature Sensor