background image

 

 

   

CPS-EC480(R2) MANUAL

                 

Camtec Power Supplies GmbH  -  Gewerbestrasse 30  -  76327 Pfinztal  -  Germany      

P.11/12 (02/2017-01-3)

 

Phone +49(721)46596-0  -   Fax +49(721)46596-77  -   

www.camtec-gmbh.com

 - 

info@camtec-gmbh.com

 

(Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death) 

 

Connections

 

Clamping Yoke Connector Specifications 

 

Input / Output connections 

Signal connections plugs 

Tightening torque min. – max. 

1,2 – 2,2Nm (blade 1,0x5,5 DIN5264 ) 

0,2 – 0,25Nm (blade 0,4x2,2 DIN5264) 

Touch-safe protection acc. to DIN VDE 0470 

IP20 plugged/ IP10 unplugged 

Not applicable 

Clamping range, min. – max. 

0,5 – 16mm² / AWG26 – AWG6 

0,2 – 1,5mm² / AWG28 – AWG14 

Solid, H05(07) V-U min. – max. 

0,5 – 16mm² 

0,2 – 1,5mm² 

Stranded, H05(07) V-U min. – max. 

6 – 16mm² 

0,2 – 1,5mm² 

Flexible, H05(07) V-U min. – max. 

0,5 – 16mm² 

0,2 – 1,5mm² 

w. plastic collar ferrule, DIN 46228 pt 4 min. – max. 

2,5 – 10mm² 

0,2 – 1,5mm² 

w. wire end ferrule, DIN 46228 pt 1, min. – max. 

2,5 – 10mm² 

0,2 – 1,5mm² 

Plug gauge in accordance with EN 60999 a x b; ø 

5,4 x 5,1mm; 5,3mm 

2,4 x 1,5mm; 2,3mm 

Pitch (P) 

10,16mm 

3,5mm 

Wire Stripping Length (fine wired) 

Nominal Cross Section 

Wire End Ferrule 

Stripping Length 

Wire End Ferrule 

Stripping Length 

0,25mm² 

H0,25/5 

5mm 

H0,25/10 HBL 

8mm 

0,5mm² 

H0,5/6 

6mm 

H0,5/12 OR 

8mm 

1,0mm² 

H1,0/6 

6mm 

H1,0/12 GE 

8mm 

2,5mm² 

H2,5/12  

12mm 

H2,5/19D BL  

14mm 

4,0mm² 

H4,0/12 

12mm 

H4,0/20 GDR 

14mm 

6,0mm² 

H6,0/20 

12mm 

H6,0/20 SW 

14mm 

10,0mm² 

H10,0/12 

12mm 

H10,0/22 EB 

15mm 

The length of ferrules is to be chosen depending on the rated voltage. The outside diameter of the plastic collar should not be larger than 
the pitch (P) 

 
 

Ordering Information 

Ordering Codes 

Product Code 

Information 

Article Number 

CPS-EC480.024(R2) 

24V 

3041104001CA 

CPS-EC480.036(R2) 

36V 

3041104002CA 

CPS-EC480.048(R2) 

48V 

3041104003CA 

CPS-EC480.060(R2) 

60V 

3041104004CA 

CPS-EC480.072(R2) 

72V 

3041104005CA 

CPS-EC480.110(R2) 

110V 

3041104006CA 

CPS-EC480.150(R2) 

150V 

3041104007CA 

CPS-EC480.220(R2) 

220V 

3041104008CA 

CPS-EC480.300(R2) 

300V 

3041104009CA 

Back Plate Kit 

Base Plate / Hart mount plate kit including screws 

2201002001CA 

 
 
 
 
 
 
 
 
 
 
 
 

 

 

Summary of Contents for 2201002001CA

Page 1: ...ontrol 1V per load line Electronic inrush current limiter 13 8Apeak Inhibit function Interlock External shutdown Efficiency up to 92 Precise dynamic response to load change Designed for long life under full stress Strong input filters Hold up time 50ms Soft start auto recovery High reliability shock vibration proof EMC meets CE norm class B Overload and short circuit protection Large terminals 4x ...

Page 2: ...ed with a 15 turn high precision potentiometer The listed values are guaranteed by the factory The tolerance of the upper margin is 0 5 The tolerance of the lower margin is 5 0 Output Current Monitoring The CPS EC power supply features a 0 5Vdc signal output It is a real time linear signal and indicates the current consumption of the load The measuring point is directly at the output connection of...

Page 3: ...ed isolation to the inputs and the output 3000Vac Sense Function Compensation 1V per load line Remote Shutdown Yes protective forced isolation to the inputs and the output 3000Vac Inhibit Function Interlock Yes protective forced isolation to the inputs and the output 3000Vac Derating 60 C 70 C 2 5 C Accuracy 1 5 interface Load Regulation 0 05 0 100 Start up from Shutdown Typ 320ms Start up from In...

Page 4: ... output Sense Compensation 1V per load line AWG22 AWG6 0 25 2 5mm Sense Aux 3000Vac to input Power Good Relay b contact AWG22 AWG6 0 25 2 5mm DC OK 3000Vac to input output All potentiometers and all the inputs and the outputs of the analogue interface provide a forced isolation It is to ensure a protective isolation for the 300Vdc DC Voltage Current adjustment range Rated DC Voltage 24Vdc 36Vdc 48...

Page 5: ...ARNING Reverse polarity of the sense lines can cause damages to the power supply unit To basically prevent from interferences enable to twist sense compensation lines To reduce inductive influences make sure that the load wires are installed close to each other Driving a pulsative load requires a large electrolytic and a ceramic capacitor Make sure that C1 C2 are not oscillating with load wires It...

Page 6: ...y setting for DC input supply The below table of values shows the hysteresis of the lower and upper threshold margins where the DC OK Relay indicates a low voltage The nominal voltage of the cell voltage of a typical lead acid battery VRLA vented GEL AGM is listed OPsZ OPzS OPzV OGi OGiV GiV types WARNING Regarding the DC output voltage setting range it is important to consider that this data shee...

Page 7: ...PS EC480 048 58 8 3 48 10 0 480W CPS EC480 060 75 6 4 60 8 0 480W CPS EC480 072 90 5 3 72 6 7 480W CPS EC480 110 137 5 3 5 110 4 4 480W CPS EC480 150 180 2 7 150 3 2 480W CPS EC480 220 264 1 8 220 2 2 480W CPS EC480 300 360 1 3 300 1 6 480W Inrush Current Limiter The unit is featured with an electronic inrush current limiter ex 230Vac 9 8Arms 13 8Apeak The built in circuit is a very precise limite...

Page 8: ...ies from each other To increase the power capability RED models can be connected in parallel For higher voltages an external decoupling diode shall be installed from the system engineer Coating Option We offer the CPS EC series with an optional coating It is to be used in e g dusty dirty high humidity area or in awaiting quick temperature changes Short circuit and corrosion at print board lines an...

Page 9: ...t in injury or death Mechanics Mechanics Stable metal aluminum housing IP20 To allow adequate convection a free air space of 50mm top bottom and 5mm sidewalls is required for active devices 15mm space from the sidewalls For free air convection it is necessary to install the unit horizontal Use the DIN Rail installation equipped standard with the patented 35mm DIN Rail brackets according to EN60275...

Page 10: ...and for active devices 15mm space from the sidewalls For proper air convection it is necessary to install the CPS EC480 One can use the DIN Rail installation equipped standard with our patented 35mm DIN Rail bracket according to EN60275 It is easy to mount dismount while snaping it onto the 35mm DIN Rail no tools necessary A wall mount back plate option is available too It is not allowed to instal...

Page 11: ... DIN 46228 pt 1 min max 2 5 10mm 0 2 1 5mm Plug gauge in accordance with EN 60999 a x b ø 5 4 x 5 1mm 5 3mm 2 4 x 1 5mm 2 3mm Pitch P 10 16mm 3 5mm Wire Stripping Length fine wired Nominal Cross Section Wire End Ferrule Stripping Length Wire End Ferrule Stripping Length 0 25mm H0 25 5 5mm H0 25 10 HBL 8mm 0 5mm H0 5 6 6mm H0 5 12 OR 8mm 1 0mm H1 0 6 6mm H1 0 12 GE 8mm 2 5mm H2 5 12 12mm H2 5 19D B...

Page 12: ...ing bolts or operation outside the specified herein specification or in an unsuitable environment has the immediate loss of warranty to follow We disclaim any responsibility for any resulting damage to persons or things 4 Note The device must not be operated without an upstream circuit breaker CB We recommend the use of B Type 16A for 230Vac and for 115Vac It is prohibited to use the unit without ...

Reviews: