CPS-EC480(R2) MANUAL

                 

Camtec Power Supplies GmbH  -  Gewerbestrasse 30  -  76327 Pfinztal  -  Germany      

P.12/12 (02/2017-01-3)

 

Phone +49(721)46596-0  -   Fax +49(721)46596-77  -   

www.camtec-gmbh.com

 - 

info@camtec-gmbh.com

 

(Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death) 

 

 

Safety regulations: Please read these instructions completely before using the equipment. Keep these 
instructions on to hand. The device may only be operated by trained specialist staff. 

 

Installation: 

1) The device is designed for devices and systems 
that meet the standard requirements for hazardous 
voltages, power, and fire prevention. 
2.) Installation and service only by trained persons. 
The AC power must be switched off. The work is to be 
labelled; accidental reconnection of the system must 
be prevented. 
3.) Opening the device, its modification, loosening 
bolts, or operation outside the specified herein 
specification or in an unsuitable environment, has the 
immediate loss of warranty to follow. We disclaim any 
responsibility for any resulting damage to persons or 
things. 
4.) Note: The device must not be operated without an 
upstream circuit breaker (CB). We recommend the use 
of B-Type 16A for 230Vac and for 115Vac. It is 
prohibited to use the unit without PE. It may be 
necessary upstream device has a power switch. 

 

Warning

Non-compliance these warnings can result in fire 
and serious injury or death.

 

1. Never operate device

 

without PE connection. 

2. Before connecting the device to the AC 
network, make wires free of voltage and assure 
accidentally switch on. 
3. Allow neat and professional cabling. 
4. Never open nor try to repair the unit. Inside 
are dangerous voltages that can cause electrical 
shock hazard. 
5. Avoid metal pieces or other conductive 
material to fall into the item

 

6. Do not operate the device in damp or wet 
conditions 
7. Do not operate the unit under EX-conditions 

 

 

 

All parameters base on 15 minutes run-in @ full load / 25°C / 230Vac 50/60Hz, as otherwise stated. 

Summary of Contents for 2201002001CA

Page 1: ...ontrol 1V per load line Electronic inrush current limiter 13 8Apeak Inhibit function Interlock External shutdown Efficiency up to 92 Precise dynamic response to load change Designed for long life under full stress Strong input filters Hold up time 50ms Soft start auto recovery High reliability shock vibration proof EMC meets CE norm class B Overload and short circuit protection Large terminals 4x ...

Page 2: ...ed with a 15 turn high precision potentiometer The listed values are guaranteed by the factory The tolerance of the upper margin is 0 5 The tolerance of the lower margin is 5 0 Output Current Monitoring The CPS EC power supply features a 0 5Vdc signal output It is a real time linear signal and indicates the current consumption of the load The measuring point is directly at the output connection of...

Page 3: ...ed isolation to the inputs and the output 3000Vac Sense Function Compensation 1V per load line Remote Shutdown Yes protective forced isolation to the inputs and the output 3000Vac Inhibit Function Interlock Yes protective forced isolation to the inputs and the output 3000Vac Derating 60 C 70 C 2 5 C Accuracy 1 5 interface Load Regulation 0 05 0 100 Start up from Shutdown Typ 320ms Start up from In...

Page 4: ... output Sense Compensation 1V per load line AWG22 AWG6 0 25 2 5mm Sense Aux 3000Vac to input Power Good Relay b contact AWG22 AWG6 0 25 2 5mm DC OK 3000Vac to input output All potentiometers and all the inputs and the outputs of the analogue interface provide a forced isolation It is to ensure a protective isolation for the 300Vdc DC Voltage Current adjustment range Rated DC Voltage 24Vdc 36Vdc 48...

Page 5: ...ARNING Reverse polarity of the sense lines can cause damages to the power supply unit To basically prevent from interferences enable to twist sense compensation lines To reduce inductive influences make sure that the load wires are installed close to each other Driving a pulsative load requires a large electrolytic and a ceramic capacitor Make sure that C1 C2 are not oscillating with load wires It...

Page 6: ...y setting for DC input supply The below table of values shows the hysteresis of the lower and upper threshold margins where the DC OK Relay indicates a low voltage The nominal voltage of the cell voltage of a typical lead acid battery VRLA vented GEL AGM is listed OPsZ OPzS OPzV OGi OGiV GiV types WARNING Regarding the DC output voltage setting range it is important to consider that this data shee...

Page 7: ...PS EC480 048 58 8 3 48 10 0 480W CPS EC480 060 75 6 4 60 8 0 480W CPS EC480 072 90 5 3 72 6 7 480W CPS EC480 110 137 5 3 5 110 4 4 480W CPS EC480 150 180 2 7 150 3 2 480W CPS EC480 220 264 1 8 220 2 2 480W CPS EC480 300 360 1 3 300 1 6 480W Inrush Current Limiter The unit is featured with an electronic inrush current limiter ex 230Vac 9 8Arms 13 8Apeak The built in circuit is a very precise limite...

Page 8: ...ies from each other To increase the power capability RED models can be connected in parallel For higher voltages an external decoupling diode shall be installed from the system engineer Coating Option We offer the CPS EC series with an optional coating It is to be used in e g dusty dirty high humidity area or in awaiting quick temperature changes Short circuit and corrosion at print board lines an...

Page 9: ...t in injury or death Mechanics Mechanics Stable metal aluminum housing IP20 To allow adequate convection a free air space of 50mm top bottom and 5mm sidewalls is required for active devices 15mm space from the sidewalls For free air convection it is necessary to install the unit horizontal Use the DIN Rail installation equipped standard with the patented 35mm DIN Rail brackets according to EN60275...

Page 10: ...and for active devices 15mm space from the sidewalls For proper air convection it is necessary to install the CPS EC480 One can use the DIN Rail installation equipped standard with our patented 35mm DIN Rail bracket according to EN60275 It is easy to mount dismount while snaping it onto the 35mm DIN Rail no tools necessary A wall mount back plate option is available too It is not allowed to instal...

Page 11: ... DIN 46228 pt 1 min max 2 5 10mm 0 2 1 5mm Plug gauge in accordance with EN 60999 a x b ø 5 4 x 5 1mm 5 3mm 2 4 x 1 5mm 2 3mm Pitch P 10 16mm 3 5mm Wire Stripping Length fine wired Nominal Cross Section Wire End Ferrule Stripping Length Wire End Ferrule Stripping Length 0 25mm H0 25 5 5mm H0 25 10 HBL 8mm 0 5mm H0 5 6 6mm H0 5 12 OR 8mm 1 0mm H1 0 6 6mm H1 0 12 GE 8mm 2 5mm H2 5 12 12mm H2 5 19D B...

Page 12: ...ing bolts or operation outside the specified herein specification or in an unsuitable environment has the immediate loss of warranty to follow We disclaim any responsibility for any resulting damage to persons or things 4 Note The device must not be operated without an upstream circuit breaker CB We recommend the use of B Type 16A for 230Vac and for 115Vac It is prohibited to use the unit without ...