background image

 

Camtec Systemelektronik GmbH – Gewerbestraße 30 – DE76327 Pfinztal – Germany 

         

p.2/4

 

10.09A

 

Phone 0049(721)46596-0  -  Fax 0049(721)46596-77 – 

www.camtec-gmbh.com

 - 

info@camtec-gmbh.com

 

(Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death) 

 

AC Input (internal selection) 

230Vac , 47...63Hz , 250…375Vdc 

AC Input Rating 

184..265Vac, 230Vac <1.1A 

Rated DC Voltage 

56Vdc(48V) 

  

 

  

  

Low DC Voltage 

38Vdc 

        

 

  

  

Rated DC Current (

s. graph

) 40°C 

2.0A 

 

 

 

 

Maximum DC Current (

s. graph

) 40°C 

3.0A 

 

 

 

 

Ripple [mVpp] (230Vac available) 

150 (20MHz) 

  

 

 

  

Load regulation 0-100% 

±0.5% 

 

 

 

 

 

 

 

 

 

 

 

Tolerance Ua adjusted 

± 1% 

 

Transient Time 

<1ms (10-100% , 100-10%)

 

Minimum Load 

0 A 

Efficiency 

90% typical 

Load Protection 

3A

  

, manual reset 

Short Circuit Protection 

Yes, auto recovery 

Input Fuse 

2x 4AT, N & L fused, UL-type! 

Output Fuse 

Thermal 3A, push to reset 

Inrush Current 

< 32A (230Vac) 

Hold Up Time (Battery full) 

4h / 1A load 

 
 
 
 
 
 
 
 
 

 

 

 

Convection 

Natural convection 

Operation Temperature 

+10°C…+40°C IEC60068-2-1 

Transport Temperature 

-15°C…+55°C IEC60068-2-1 

Storage Temperature 

+10°C…+30°C IEC60068-2-1 

EMI 

EN55022 class B / EN61000-3-2 

EMS 

EN61000-6-2,3 

Safety 

(IEC)EN60950-1 

Safety class 1(A) 

VDE0805, VDE0100 

Air & Surface Leakage Paths 

> 8mm 

Input/output 

Galvanic insulated 

AC Fail Relay (galv. insulated) 

≤48Vdc/500mA , ≤30Vac/500mA 

DC Fail Relays (galv. insulated)  ≤48Vdc/500mA , ≤30Vac/500mA 

(option)

 

Relative Humidity (+25°C) 

≤95% , no condensations 

Pollution Degree 

2 (EN50178) 

Climatic Class 

3K3 (EN60721) 

Dimensions (HxWxD(T)) 

2U 84WU D=280mm 

Weight 

9800g 

Connector AC 

C14 Schaffner IEC60320-1, L+N lines 
fused. Dismounting protected by a 
securing clip Schurter 4700.0001 

Connectors DC 

 

Phoenix 1840599 DFK-PC4/6-GF-7,62 
Female. Dismounting protection with 
M3 threads for the mating plug. 

 

Connector DC-Fail-Message 

SUB-D 9pole female DIN41652 T1 

 

 
 
Specification: 

The  DCUPS2U-Series  is  designed  as  an  uninterruptable  power  supply  for  telecommunication  and  data 
application use. Its regulated DC of 90% makes the DCUPS2U robust, economical and reliable. Camtec power 
supplies  are  traditionally  made  with  high-end  low  ESR  electrolytic  output  capacitors  with  withstanding 
+125°C  temperature.  Our  capacitors  are  rather  designed  over  for  longer  lifetime  and  longer  hold  up  times. 
The DCUPS2U is short circuit and zero load stability protected. It has a thermal overload fuse at the output to 
protect  the  connected  load.  It  is  protected  against  high  transient  and  provides  very  good  interference 
resistance.  We use IP20 stabile aluminium housings with ventilation slots in accordance to the  demanding 
VDE norms. The plus pole has an internal connection to ground. The AC-Line connector and the DC-Output 
connector  has  securing  clip  and  screw  fitting  to  avoid  accidential  removal  of  the  connected  cabeling.  The 
DCUPS2U  has  a  built  in  AC-Fail  detection  and  the  message  is  available  at  the  output  connector  galvanic 
insulated.  A  DC-fail-function-  message  for  the  battery  charger  power  supply  and  the  main  power  supply  is 
optional available; each relay is floating galvanic insulated. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

Battery 
use 

Summary of Contents for DCUPS2U4AH

Page 1: ...Specification Metal housing 90 efficiency 10 C 40 C ambient Free air convection Galvanic insulated Continuous short circuit idle proof Overload low voltage protected Soft start auto recovery Hold up time 30ms Minimum load 0A EMI EMS EN61000 6 2 3 EN55022 class B pole connected to GND housing According to IEC EN 60950 1 Extended monitoring Thermal load protection AC Fail message Built in high relia...

Page 2: ...ions Pollution Degree 2 EN50178 Climatic Class 3K3 EN60721 Dimensions HxWxD T 2U 84WU D 280mm Weight 9800g Connector AC C14 Schaffner IEC60320 1 L N lines fused Dismounting protected by a securing clip Schurter 4700 0001 Connectors DC Phoenix 1840599 DFK PC4 6 GF 7 62 Female Dismounting protection with M3 threads for the mating plug Connector DC Fail Message SUB D 9pole female DIN41652 T1 Specific...

Page 3: ...th 50 60Hz The output voltages is floating and has no ohmic reference to ground d If testing output voltages are 60Vdc remain to security directives Use only isolated screw drivers to adjust output voltages Function Table and Messages optional available Indicators AC Line o k green LED AC Fail Relay Contact Battery o k LED green Battery Low LED red Battery Charge LED yellow Piezo Sound Interval 30...

Page 4: ...vised to use the same battery type as the installed one to DC UPS The battery type is the Panasonic LC R124R5P 12V 4 5Ah We recommend the batteries to change after 2 years cycle operation to prevent malfunctions Safety Instructions Please read all warnings and advices carefully before installing or operating the DCUPS2U Retain this operation manual always ready to hand The DCUPS2U must be installe...

Reviews: