Camtec Systemelektronik GmbH – Gewerbestraße 30 – DE76327 Pfinztal – Germany
p.2/4
10.09A
Phone 0049(721)46596-0 - Fax 0049(721)46596-77 –
www.camtec-gmbh.com
-
info@camtec-gmbh.com
(Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death)
AC Input (internal selection)
230Vac , 47...63Hz , 250…375Vdc
AC Input Rating
184..265Vac, 230Vac <1.1A
Rated DC Voltage
56Vdc(48V)
Low DC Voltage
38Vdc
Rated DC Current (
s. graph
) 40°C
2.0A
Maximum DC Current (
s. graph
) 40°C
3.0A
Ripple [mVpp] (230Vac available)
150 (20MHz)
Load regulation 0-100%
±0.5%
Tolerance Ua adjusted
± 1%
Transient Time
<1ms (10-100% , 100-10%)
Minimum Load
0 A
Efficiency
90% typical
Load Protection
3A
, manual reset
Short Circuit Protection
Yes, auto recovery
Input Fuse
2x 4AT, N & L fused, UL-type!
Output Fuse
Thermal 3A, push to reset
Inrush Current
< 32A (230Vac)
Hold Up Time (Battery full)
4h / 1A load
Convection
Natural convection
Operation Temperature
+10°C…+40°C IEC60068-2-1
Transport Temperature
-15°C…+55°C IEC60068-2-1
Storage Temperature
+10°C…+30°C IEC60068-2-1
EMI
EN55022 class B / EN61000-3-2
EMS
EN61000-6-2,3
Safety
(IEC)EN60950-1
Safety class 1(A)
VDE0805, VDE0100
Air & Surface Leakage Paths
> 8mm
Input/output
Galvanic insulated
AC Fail Relay (galv. insulated)
≤48Vdc/500mA , ≤30Vac/500mA
DC Fail Relays (galv. insulated) ≤48Vdc/500mA , ≤30Vac/500mA
(option)
Relative Humidity (+25°C)
≤95% , no condensations
Pollution Degree
2 (EN50178)
Climatic Class
3K3 (EN60721)
Dimensions (HxWxD(T))
2U 84WU D=280mm
Weight
9800g
Connector AC
C14 Schaffner IEC60320-1, L+N lines
fused. Dismounting protected by a
securing clip Schurter 4700.0001
Connectors DC
Phoenix 1840599 DFK-PC4/6-GF-7,62
Female. Dismounting protection with
M3 threads for the mating plug.
Connector DC-Fail-Message
SUB-D 9pole female DIN41652 T1
Specification:
The DCUPS2U-Series is designed as an uninterruptable power supply for telecommunication and data
application use. Its regulated DC of 90% makes the DCUPS2U robust, economical and reliable. Camtec power
supplies are traditionally made with high-end low ESR electrolytic output capacitors with withstanding
+125°C temperature. Our capacitors are rather designed over for longer lifetime and longer hold up times.
The DCUPS2U is short circuit and zero load stability protected. It has a thermal overload fuse at the output to
protect the connected load. It is protected against high transient and provides very good interference
resistance. We use IP20 stabile aluminium housings with ventilation slots in accordance to the demanding
VDE norms. The plus pole has an internal connection to ground. The AC-Line connector and the DC-Output
connector has securing clip and screw fitting to avoid accidential removal of the connected cabeling. The
DCUPS2U has a built in AC-Fail detection and the message is available at the output connector galvanic
insulated. A DC-fail-function- message for the battery charger power supply and the main power supply is
optional available; each relay is floating galvanic insulated.
Battery
use