background image

 

Camtec Power Supplies GmbH  -  Gewerbestrasse 30  -  76327 Pfinztal  -  Germany        

p. 1/5 (07.2014-04-1)

 

Phone +49(721)46596-0  -   Fax +49(721)46596-77  -   

www.camtec-gmbh.com

 - 

info@camtec-gmbh.com

 

(Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death

 

 

HSE03201LIRC         DIN Rail 

 

 

 

 

 

 

 

 

 

     Made in Germany 

320 Watts Power Supply -20…+70°C 
115/230Vac Input Voltage – low inrush 

 

Short Specification: 

 

Metal housing 

 

Up to 91% efficiency 

 

-20°C...+60°C full output power 

 

C/V curve down to 0V, no fold back 

 

Free air convection 

 

Galvanic insulated 

 

Continuous short circuit protected  

 

Overload & low voltage protected 

 

Open Circuit Proof 

 

Soft start & auto-recovery 
 
 

 

Hold up time >30ms 

 

Switching frequency typ. 100KHz 

 

EMI/EMS EN61000-6-2,3, EN55022 class B 

 

PFC: EN61000-3-2 class A 

 

IEC(EN)60950-1 

 

Series & parallel operation 

 

DIN Rail 35mm  

 

Screw terminals AWG21...AWG10 

 

24 hours burn in test 

 

High reliability, shock & vibration resistant 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Models 

Voltage 

Current 

HSE03201.05T 

5V-9V 

18A 

HSE03201.12T 

12V 

18A 

HSE03201.15T 

15V 

17A 

HSE03201.24T 

24V 

13.5A 

HSE03201.36T 

36V 

8.9A 

HSE03201.48T 

48V 

6.7A 

HSE03201.60T 

60V 

5.4A 

Summary of Contents for HSE03201 Series

Page 1: ...housing Up to 91 efficiency 20 C 60 C full output power C V curve down to 0V no fold back Free air convection Galvanic insulated Continuous short circuit protected Overload low voltage protected Open Circuit Proof Soft start auto recovery Hold up time 30ms Switching frequency typ 100KHz EMI EMS EN61000 6 2 3 EN55022 class B PFC EN61000 3 2 class A IEC EN 60950 1 Series parallel operation DIN Rail ...

Page 2: ... Vout 1 Load regulation 0 5 10 100 100 10 Response to Load Change 1ms 10 100 100 10 Short Circuit Protection Continuous Open Circuit Proof Continuous Efficiency 91 typical at 90 load Load Protection 1 2x Irated with auto recovery Voltage Protection 140 of Uout with auto recovery Hold Up Time 30ms 230Vac Inrush Current 10 6Aeff 15Apeak active inrush current limiter inside MCB Circuit Breaker 4A typ...

Page 3: ...Voltage Protection Derating OT Over Temperature The maximum ambient temperature is 70 C There is temperature protection inside the power supply When the temperature exceeds a certain level the HSR03201 will be shut down The unit provides an automatic restart when the temperature returns to applicable conditions OVP Over Voltage Protection Exceeding the OVP results into ticker mode Resuming the fai...

Page 4: ...which apply the voltage with a slow ramp b Connect L1 and N together as well as all output poles c Use only AC test voltages with 50 60Hz The output voltage is floating and has no ohmic reference to ground d If testing output voltages are 60Vdc remain to security directives Use only isolated screw drivers to adjust output voltages Mechanics Installation Instruction of the HSR03201 Stable metal alu...

Page 5: ...evention 2 Installation and service only by trained persons The AC power must be switched off The work is to be labeled accidental reconnection of the system must be prevented 3 Opening the device its modification loosening bolts or operation outside the specified herein specification or in an unsuitable environment has the immediate loss of warranty to follow We disclaim any responsibility for an...

Reviews: