(Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death
Safety Test
T
A
B
C
¹)
D
Type test and factory tests are
conducted by the manufacturer.
Do not repeat the test in field.
Field test rules:
Type Test
60s
2500Vac 3000Vac 500Vdc
3000Vac
Factory Test
5s
2000Vac 2000Vac 500Vdc
2000Vac
Field Test
2s
2000Vac 2000Vac 500Vdc
2000Vac
¹)
≥
60Vdc = 2400Vdc
a)
Use approriate test equipment which apply the voltage with a slow ramp
b)
Connect L1 and N together, as well as all output poles
c)
Use only AC test-voltages with 50/60Hz. The output voltage is floating and has
no ohmic reference to ground.
d)
If testing output voltages are
≥
60Vdc remain to security directives.
Use only isolated screw drivers to adjust output voltages.
Mechanics & Installation Instruction of the HSR03201
Stable metal/aluminium housing IP20. To allow adequate convection, a free air space of 50mm (top/bottom) and 5mm (sidewalls) is
required; and to active devices 15mm space from the sidewalls. Patented 35mm DIN-Rail bracket meet EN60275. It is easy to
mount/dismount while snaping it onto the 35mm DIN-Rail - no tools necessary.
Other mounting direction then shown are not evaluated from our engineering team and may need a power derating or it can cause a
derating of the product life time.