(Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Safety Test 

 

¹)

 

Type test and factory tests are  
conducted by the manufacturer.  
Do not repeat the test in field.  
Field test rules:

 

Type Test 

60s 

2500Vac  3000Vac  500Vdc 

3000Vac 

Factory Test 

5s 

2000Vac  2000Vac  500Vdc 

2000Vac 

Field Test 

2s 

2000Vac  2000Vac  500Vdc 

2000Vac 

                                                               ¹) 

60Vdc = 2400Vdc 

 

a) 

Use approriate test equipment which apply the voltage with a slow ramp 

b) 

Connect L1 and N together, as well as all output poles 

c) 

Use only AC test-voltages with 50/60Hz. The output voltage is floating and has  
no ohmic reference to ground. 

d) 

If testing output voltages are 

60Vdc remain to security directives.  

Use only isolated screw drivers to adjust output voltages. 
 

Mechanics & Installation Instruction of the HSR03201 

Stable metal/aluminium housing IP20. To allow adequate convection, a free air space of 50mm (top/bottom) and 5mm (sidewalls) is 
required; and to active devices 15mm space from the sidewalls. Patented 35mm DIN-Rail bracket meet EN60275. It is easy to 
mount/dismount while snaping it onto the 35mm DIN-Rail - no tools necessary. 
Other mounting direction then shown are not evaluated from our engineering team and may need a power derating or it can cause a 
derating of the product life time. 

Summary of Contents for HSE03201 Series

Page 1: ...housing Up to 91 efficiency 20 C 60 C full output power C V curve down to 0V no fold back Free air convection Galvanic insulated Continuous short circuit protected Overload low voltage protected Open Circuit Proof Soft start auto recovery Hold up time 30ms Switching frequency typ 100KHz EMI EMS EN61000 6 2 3 EN55022 class B PFC EN61000 3 2 class A IEC EN 60950 1 Series parallel operation DIN Rail ...

Page 2: ... Vout 1 Load regulation 0 5 10 100 100 10 Response to Load Change 1ms 10 100 100 10 Short Circuit Protection Continuous Open Circuit Proof Continuous Efficiency 91 typical at 90 load Load Protection 1 2x Irated with auto recovery Voltage Protection 140 of Uout with auto recovery Hold Up Time 30ms 230Vac Inrush Current 10 6Aeff 15Apeak active inrush current limiter inside MCB Circuit Breaker 4A typ...

Page 3: ...Voltage Protection Derating OT Over Temperature The maximum ambient temperature is 70 C There is temperature protection inside the power supply When the temperature exceeds a certain level the HSR03201 will be shut down The unit provides an automatic restart when the temperature returns to applicable conditions OVP Over Voltage Protection Exceeding the OVP results into ticker mode Resuming the fai...

Page 4: ...which apply the voltage with a slow ramp b Connect L1 and N together as well as all output poles c Use only AC test voltages with 50 60Hz The output voltage is floating and has no ohmic reference to ground d If testing output voltages are 60Vdc remain to security directives Use only isolated screw drivers to adjust output voltages Mechanics Installation Instruction of the HSR03201 Stable metal alu...

Page 5: ...evention 2 Installation and service only by trained persons The AC power must be switched off The work is to be labeled accidental reconnection of the system must be prevented 3 Opening the device its modification loosening bolts or operation outside the specified herein specification or in an unsuitable environment has the immediate loss of warranty to follow We disclaim any responsibility for an...

Reviews: