Camtec Power Supplies GmbH  -  Gewerbestrasse 30  -  76327 Pfinztal  -  Germany        

p. 5/5 (07.2014-04-1)

 

Phone +49(721)46596-0  -   Fax +49(721)46596-77  -   

www.camtec-gmbh.com

 - 

info@camtec-gmbh.com

 

(Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death

 

 

 

Ordering Codes 

Model (DIN-Rail standard)  Information 

Camtec Article Number

 

HSE03201.05T 

5V 

3041056099CA 

HSE03201.12T 

12V 

3041056014CA

 

HSE03201.15T 

15V 

3041056015CA

 

HSE03201.24T 

24V 

3041056017CA

 

HSE03201.36T 

36V 

3041056020CA

 

HSE03201.48T 

48V 

3041056018CA

 

HSE03201.60T 

60V 

3041056019CA

 

Connector Power Good **  2pole, 10 pcs per pack, lead space 5,08mm 

3520037 

** Note that the power good contact connectors are not a part of the power supply and require separate order 

 

 

Safety regulations: Please read these instructions completely before using the equipment. Keep these 
instructions on to hand. The device may only be operated by trained specialist staff. 

 

Installation: 

1) The device is designed for devices and systems 
that meet the standard requirements for hazardous 
voltages, power and fire prevention. 
2.) Installation and service only by trained persons. 
The AC power must be switched off. The work is to be 
labeled; accidental reconnection of the system must 
be prevented. 
3.) Opening the device, its modification, loosening 
bolts or operation outside the specified herein 
specification or in an unsuitable environment, has the 
immediate loss of warranty to follow. We disclaim any 
responsibility for any resulting damage to persons or 
things. 
4.) Note: The device must not be operated without an 
upstream circuit breaker (CB). We recommend the use 
of a 4A type-B for 230Vac and 6A type-B for 115Vac. It 
is prohibited to use the unit without PE. It may be 
necessary upstream device has a power switch. 

 

Warning:

 

Non-compliance can result in fire and serious injury or 
death. 

1. Operate the appliance without PE connection. 
2. Before connecting the device to the AC 
network, make wires free of voltage and assure 
accidently switch on. 
3. Allow neat and professional cabling. 
4. Never open nor try to repair the unit. Inside 
are dangerous voltages that can cause electrical 
shock hazard. 
5. Avoid metal pieces or other conductive 
material to fall into the item

 

6. Do not operate the device in damp or wet 
conditions 
7. Do not operate the unit under EX-conditions

 

 

All parameters base on 15 minutes run-in @ full load / 25°C / 230Vac 50/60Hz, as otherwise stated. 

Summary of Contents for HSE03201 Series

Page 1: ...housing Up to 91 efficiency 20 C 60 C full output power C V curve down to 0V no fold back Free air convection Galvanic insulated Continuous short circuit protected Overload low voltage protected Open Circuit Proof Soft start auto recovery Hold up time 30ms Switching frequency typ 100KHz EMI EMS EN61000 6 2 3 EN55022 class B PFC EN61000 3 2 class A IEC EN 60950 1 Series parallel operation DIN Rail ...

Page 2: ... Vout 1 Load regulation 0 5 10 100 100 10 Response to Load Change 1ms 10 100 100 10 Short Circuit Protection Continuous Open Circuit Proof Continuous Efficiency 91 typical at 90 load Load Protection 1 2x Irated with auto recovery Voltage Protection 140 of Uout with auto recovery Hold Up Time 30ms 230Vac Inrush Current 10 6Aeff 15Apeak active inrush current limiter inside MCB Circuit Breaker 4A typ...

Page 3: ...Voltage Protection Derating OT Over Temperature The maximum ambient temperature is 70 C There is temperature protection inside the power supply When the temperature exceeds a certain level the HSR03201 will be shut down The unit provides an automatic restart when the temperature returns to applicable conditions OVP Over Voltage Protection Exceeding the OVP results into ticker mode Resuming the fai...

Page 4: ...which apply the voltage with a slow ramp b Connect L1 and N together as well as all output poles c Use only AC test voltages with 50 60Hz The output voltage is floating and has no ohmic reference to ground d If testing output voltages are 60Vdc remain to security directives Use only isolated screw drivers to adjust output voltages Mechanics Installation Instruction of the HSR03201 Stable metal alu...

Page 5: ...evention 2 Installation and service only by trained persons The AC power must be switched off The work is to be labeled accidental reconnection of the system must be prevented 3 Opening the device its modification loosening bolts or operation outside the specified herein specification or in an unsuitable environment has the immediate loss of warranty to follow We disclaim any responsibility for an...

Reviews: