60
To adjust the high-fire setting of the
High-End Valve
(AV800)
1) Press
[DIAGNOSTICS]
button
2) Press
[Diagnostic Tests]
button
3) Press
[Maximum Modulation]
button
4) Press
[Start Test]
to operate the boiler at max fire for 5 minutes.
Increase CO
2
Decrease CO
2
High Fire Adjustment
Counter- Clockwise
Clock Wise
With the appliance firing at high fire check the manifold pressure at the discharge of the
High-End Gas Valve
and compare it to the
manifold pressure provided on the rating plate.
When the correct combustion values are achieved replace the cap back on to the gas valve.
To adjust the low fire setting of the
Low-End Valve
(AV1000
– 4000)
Use the
Advantus
Control Panel
1. Press
[DIAGNOSTICS]
button
2. Press
[Diagnostic Tests]
button
3. Move the firing rate slider to firing rate (%) indicated on test reports.
4. Press
[Start Test]
to operate the boiler at this firing rate for 5 minutes.
Increase CO
2
Decrease CO
2
Low Fire Adjustment
Clockwise
Counter-Clock Wise
After adjusting the screw wait a moment for the combustion levels to stabilize before attempting to make any further adjustments. Continue
this procedure until combustion levels are satisfied.
When the correct combustion values are achieved replace the screw cap back on to the gas valve.
To adjust the high fire setting of the
Low-End Valve
(AV1000
– 4000)
The high fire setting of the
Low-End Gas Valve
must be set at a point just before the Siemens gas valve is activated. This will vary from
model to model and the installer will need to monitor at which point on the VFD that the transition occurs. It is advised to set the
High-
End Gas Valve
at 2 Hz below where the transition occurs. This transition has been set and tested at the factory and should normally not
require adjustment
Use the
Advantus
Control Panel
1. Press
[DIAGNOSTICS]
button
2. Press
[Diagnostic Tests]
button
3. Move the firing rate slider to firing rate (%) indicated on test reports.
4. Press
[Start Test]
to operate the boiler at this firing rate for 5 minutes.
Increase CO
2
Decrease CO
2
High Fire Adjustment
Counter- Clockwise
Clock Wise
After adjusting the screw wait a moment for the combustion levels to stabilize before attempting to make any further adjustments.
Continue this procedure until combustion levels are satisfied.
When the correct combustion values are achieved replace the screw cap back on to the gas valve.
Summary of Contents for ADVANTUS AVH 500
Page 2: ......
Page 3: ......
Page 38: ...31 Figure 23 Recommended Piping with Reverse Return and Variable Primary Flow...
Page 88: ...81 PART 12 EXPLODED VIEW Figure A...
Page 89: ...82 Figure B FAN BURNER ASSEMBLY AV500 600 some items may not be as shown...
Page 90: ...83 Figure C FAN BURNER ASSEMBLY AV800 4000 some items may not be as shown...
Page 91: ...84 Figure D Figure E...
Page 92: ...85 Figure F Figure G...
Page 93: ...86 Figure H CONTROL BOARD ASSEMBLY...
Page 100: ...93 PART 13 ELECTRICAL DIAGRAMS...
Page 101: ...94...
Page 102: ...95...