background image

 

appliance remaining connected to the common venting system placed in operation, while the 
other appliances remaining connected to the common venting system are not in operation. 
 

a)  Seal any unused openings in the common venting system. 
b)  Visually inspect the venting system for proper size and horizontal pitch and determine 

that there is no blockage, restriction, leakage, corrosion or other deficiency, which could 
cause an unsafe condition. 

c)  Insofar as is practical, close all building doors and windows and all doors between the 

space in which the appliances remaining connected to the common venting system are 
located and other spaces of the building. 

 
Turn on the clothes dryers and any appliances not connected to the common venting system. 
Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at 
maximum speed, do not operate a summer exhaust fan. Close fireplace dampers.  
 

d)  Place in operation the appliance being inspected. Follow the lighting instructions. Adjust 

thermostat so that appliance operates continuously. 

 

e)  Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. 

Use the flame of a match or candle or smoke from a cigarette. 

 

f)  After it has been determined that each appliance remaining connected to the common 

venting system properly vents when tested as outlined above, return doors, windows, 
exhaust fans, fireplace dampers and any other gas-burning appliance to their previous 
condition of use. 

 

g)  Any improper operation of the common venting system must be corrected so that the 

installation conforms to the National Fuel Gas Code, ANSI Z223.1 or CAN/CGA B149, 
Installation Codes. When resizing any portion of the common venting system, the 
common venting system should be resized to approach the minimum size as determined 
using the appropriate tables in Part 11 of the National Fuel Gas Code, ANSI Z223.1 or 
CAN/CGA B149, Installation Codes. 

 
Heat exchanger surfaces and vent piping should be checked every six months for deterioration 
and carbon deposits. Remove all soot or other obstructions from the chimney and flue, which 
might impede draft action. Replace any damaged or deteriorated parts of the venting system. 
 
A qualified service technician should follow this procedure when inspecting and cleaning the 
heat exchanger and vent pipe. 
  

1.  Turn off electrical power and close main manual gas shut-off and allow boiler to cool 

down 

2.  Remove the boiler draft diverter and vent pipe running to chimney. 

  Check heat exchanger, vent and chimney for obstruction and clean as 

necessary. 

3.  Remove burner tray from boiler and vacuum top heat exchanger and coils. 
4.  Reinstall parts removed in steps 2 and 3. 

  Be sure that vent pipe has proper pitch and is properly sealed. 

5.  Restore electrical power and gas supply to boiler. 

  Place boiler in operation using lighting instructions provided. 

  Check for gas leaks and proper vent operation. 

Summary of Contents for BLUE-FLAME Series

Page 1: ...nce WHAT TO DO IF YOU SMELL GAS o Do not try to light any appliance o Do not touch any electrical switch do not use any phone in your building o Immediately call your gas supplier from a neighbour s p...

Page 2: ...9 WARNING REGARDING CHILLED WATER SYSTEMS 8 10 PIPING OF BOILER TO THE SYSTEM FIG 3 8 11 PLACING BOILER IN OPERATION 10 12 CHECK OUT OF IGNITION SYSTEM SAFETY SHUT OFF DEVICE 10 13 LOW WATER TEMPERAT...

Page 3: ...by the authority having jurisdiction the installation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers ANSI ASME CSD 1 The qualified installer shall instru...

Page 4: ...to combustibles as follows TOP 12 SIDES 12 REAR 12 VENT 6 3 PROVIDE AIR FOR COMBUSTION AND VENTILATION Provisions for combustion and ventilation air must be in accordance with section 5 3 Air for comb...

Page 5: ...ff and remote controller use terminal strip provided inside control panel Refer to wiring diagram provided with boiler 5 GAS SUPPLY AND PIPING This boiler is intended to operate at inlet gas pressures...

Page 6: ...installations always consider the use of a shelter such as a garden shed in lieu of direct exposure of the appliance to the elements The additional protection afforded by the shelter will help to min...

Page 7: ...ove return doors windows exhaust fans fireplace dampers and any other gas burning appliance to their previous condition of use g Any improper operation of the common venting system must be corrected s...

Page 8: ...6 Three venting options are available for this boiler See Figure 1 below for details Standard Venting Outdoor Venting Sidewall Venting Side View Figure 1...

Page 9: ...relief valve sized in accordance with ASME Boiler and Pressure Vessel Code Section IV Heating Boilers The relief valve is to be installed in the vertical position and mounted in the hot water outlet N...

Page 10: ...means to prevent gravity circulation of chilled water through the boiler Chilled water in the boiler will create condensate on the boiler tubes which will collect in the combustion chamber causing co...

Page 11: ...tion level it must be provided with a low water cutoff device at the time of boiler installation Available from factory To eliminate trapped air install venting devices at high points in the system as...

Page 12: ...ter level in expansion tank If level exceeds of tank volume air is still trapped in system Shut down boiler and continue to run pumps Within 3 days of start up recheck all air vents and expansion tank...

Page 13: ...e after 15 minutes c If the inlet temperature is less than 110 F slowly close outlet valve until the inlet temperature climbs to 110 F d If the inlet temperature is greater than 110 F but not greater...

Page 14: ...ns Figure 5 15 PILOT AND MAIN BURNER FLAMES To maintain safe operation and the greatest efficiency of the boiler check the main burner and pilot burner every six months for proper flame characteristic...

Page 15: ...off power and close main manual gas valve Allow burners to cool before removal 2 Loosen union and remove main burner tray assembly from boiler 3 Remove and thoroughly clean burners Check all ports and...

Page 16: ...e ignition electrode using sandpaper Once the pilot appears to be properly set reinstall it into the boiler making sure to properly tighten the pilot line connection Once the spark is satisfactory ope...

Page 17: ...tion 15 of this manual After the first season of operation inspect the heat exchanger and venting Follow the detailed instructions in section 6 of this manual CAUTION Label all wires prior to disconne...

Page 18: ...ime to light the pilot if air is not present in the pilot line If pilot fails to light and you suspect air in the line close the main manual valve and repeat lighting steps 1 thru 5 7 Once the pilot l...

Page 19: ...lame Adjust if necessary Remove pilot and ensure that spark electrode is clean and properly located 5 Pilot lights but main burner does not fire Ensure that main firing valve is in OPEN position Check...

Page 20: ...CAL DIAGRAMS Each Blue Flame boiler will be provided with its own wiring diagram to guarantee that any options ordered with the unit are properly detailed The following diagrams 99 5020 and 99 5021 ar...

Page 21: ...19...

Page 22: ...20...

Page 23: ...21 21 EXPLODED VIEW...

Page 24: ...22 22 BLUE FLAME REPLACEMENT PARTS LIST...

Page 25: ...standard warranty 2 Years six through ten replacement purchase price pro rated at the following schedule Year six 60 Year seven 65 Year eight 70 Year nine 75 Year ten 80 of the current list price of...

Page 26: ...uilt water heaters and heating boilers as well as a into every single unit For more information supplier of specialty HVAC products Our service line is open 24 hours 7 days a week on our innovative pr...

Reviews: