5
Table 2: DynaMax HS Wall Hung Service Clearances
Model
Service Clearance, Inches (cm)
Front
Top
Right Side
Left Side
Rear
80
24” (61cm)
3” (8 cm)
4” (10 cm)
4” (10 cm)
0” (0 cm)
100
24” (61cm)
3” (8 cm)
4” (10 cm)
4” (10 cm)
0” (0 cm)
150
24” (61cm)
3” (8 cm)
4” (10 cm)
4” (10 cm)
0” (0 cm)
200
24” (61cm)
3” (8 cm)
4” (10 cm)
4” (10 cm)
0” (0 cm)
250
24” (61cm)
3” (8 cm)
4” (10 cm)
4” (10 cm)
0” (0 cm)
Figure 3: DynaMax HS Wall Hung Model Dimensions
Table 3: Appliance Dimensions and Specifications
Model
Depth Dim.
"A" [in.]
Dim.
"B"
[in.]
Equivalent Length of Vent & Air
Intake Pipes at Recommended
Diameter, [in.]
Water
Connection
at Boiler
[in.] NPT
Gas Connection
at Boiler [in.] NPT
Over 25'
and up to
100'
Over 15'
and up to
25'
Up to 15'
80
16 1/2
12
3
3
2
1
1/2
100
16 1/2
12
3
3
2
1
1/2
150
16 1/2
12
3
3
2
1
1/2
200
23 1/2
19
3
3
2
1
1/2
250
23 1/2
19
3
3
2
1 1/4
1/2
Maintain minimum specified clearances for adequate operation. All installations must allow sufficient space for servicing the vent
connections, water pipe connections, circulating pump, bypass piping and other auxiliary equipment, as well as the appliance
Summary of Contents for DynaMax DMH081
Page 2: ......
Page 68: ...65 PART 14 EXPLODED VIEW PARTS LIST DYNAMAX HS WALL HUNG...
Page 69: ...66 DYNAMAX HS FLOOR MOUNT...
Page 76: ...73 PART 15 ELECTRICAL DIAGRAMS 15 1 DM 80 299 INTERNAL WIRING DIAGRAM...
Page 77: ...74 15 2 DM 399 800 INTERNAL WIRING DIAGRAM...
Page 78: ...75...