6
Table 4: DynaMax HS Floor Mount Service Clearances
Model
Service Clearance, Inches (cm)
Front
Top
Right Side
Left Side
Rear
210
12” (31cm)
24” (61cm)
0” (0cm)
12” (31cm)
14” (36 cm)
260
12” (31cm)
24” (61cm)
0” (0cm)
12” (31cm)
14” (36 cm)
299
12” (31cm)
24” (61cm)
0” (0cm)
12” (31 cm)
14” (36cm)
399
12” (31cm)
24” (61cm)
0” (0cm)
12” (31 cm)
14” (36 cm)
500
12” (31cm)
24” (61cm)
0” (0cm)
12” (31 cm)
14” (36 cm)
600
12” (31cm)
24” (61cm)
0” (0cm)
12” (31 cm)
14” (36cm)
700
12” (31cm)
24” (61cm)
0” (0cm)
12” (31 cm)
14” (36 cm)
800
12” (31cm)
24” (61cm)
0” (0cm)
12” (31 cm)
14” (36 cm)
Figure 4: DynaMax HS Floor Mount Model Dimensions
Table 5: Appliance Dimensions and Specifications
Model
Dim.
"A"
[in.]
Dim.
"B"
[in.]
Dim.
"C"
[in.]
Dim.
"D"
[in.]
Dim.
"E"
[in.]
Dim.
"F"
[in.]
Dim.
"J"
[in.]
Equivalent Length of Vent & Air Intake
Pipes at Recommended Diameter, [in.]
Water
Conn.
at
Heater
[in.]
NPT
Gas
Conn.
at
Boiler
[in.]
NPT
Category IV
CAT.II
Comb.
Vents
Over 25'
and up
to 100'
Over 15'
and up
to 25'
Up to
15'
210
36
22 3/4
14 1/4
23
24 1/4
34 1/4
32
3
3
2
4
1
1/2
260
36
22 3/4
14 1/4
23
24 1/4
34 1/4
32
3
3
2
4
1 1/4
1/2
299
47 1/8
34 7/8
14
23
29 7/8
33 7/8
32
4
3
3
5
1 1/4
3/4
399
47 1/8
34 7/8
14
23
29 7/8
33 7/8
32
4
3
3
5
1 1/2
1
500
47 1/8
34 7/8
14
23
29 7/8
33 7/8
32
4
3
3
6
1 1/2
1
600
47 1/8
36 1/4
14
23
30 3/4
38
40 1/2
4
3
3
6
2
1
700
47 1/8
36 1/4
14
23
30 3/4
38
40 1/2
4 (Air), 6
(Vent)
4
4
7
2
1
800
47 1/8
36 1/4
14
23
30 3/4
38
40 1/2
5 (Air), 6
(Vent)
5
5
7
2
1
Maintain minimum specified clearances for adequate operation. All installations must allow sufficient space for servicing the vent
connections, water pipe connections, circulating pump, bypass piping and other auxiliary equipment, as well as the appliance
Summary of Contents for DynaMax DMH081
Page 2: ......
Page 68: ...65 PART 14 EXPLODED VIEW PARTS LIST DYNAMAX HS WALL HUNG...
Page 69: ...66 DYNAMAX HS FLOOR MOUNT...
Page 76: ...73 PART 15 ELECTRICAL DIAGRAMS 15 1 DM 80 299 INTERNAL WIRING DIAGRAM...
Page 77: ...74 15 2 DM 399 800 INTERNAL WIRING DIAGRAM...
Page 78: ...75...