17
condominiums, apartments and motels and typically used in
conjunction with tempering valves to achieve temperature
control.
Table 11: Flow and Pressure Drop at a Given
Temperature Rise (Hydronic Heating)
Input,
Btu/Hr
30 °F (16.7 °C)
35 °F (19.4 °C)
Temp Rise
Temp Rise
USGPM
(min.
flow)
∆∆∆∆
P Ft.
USGPM.
(min.
flow)
∆∆∆∆
P Ft.
5.0
8.2
4.3
6.2
100,000
6.3
12.3
5.4
9.4
150,000
9.5
10.4
8.1
7.8
199,000
12.6
7.2
10.8
5.8
250,000
15.8
11.5
13.5
8.7
299,000
18.9
9.3
16.2
7.0
399,000
25.2
8.4
21.6
6.3
500,000
31.5
9.2
27.0
6.9
600,000
38.8
17.5
32.0
11.8
700,000
45.3
18.2
40.0
14.4
800,000
51.8
23.5
43.0
16.0
Table 12: Flow and Pressure Drop at a Given
Temperature Rise (DHW)
Input,
Btu/Hr
20 °F (11.1 °C)
Temp Rise
USGPM
(min.
flow)
∆∆∆∆
P Ft.
80,000
7.5
11.5
100,000
9.4
26.9
150,000
14.0
27.8
199,000
19.2
25.9
250,000
23.5
28.3
299,000
28.8
25.8
399,000
38.4
23.9
500,000
48.6
29.4
600,000
57.6
34.2
700,000
70.4
40.0
800,000
77.6
43.2
DynaMax HS Floor Mount Piping Diagrams
Summary of Contents for DynaMax DMH081
Page 2: ......
Page 68: ...65 PART 14 EXPLODED VIEW PARTS LIST DYNAMAX HS WALL HUNG...
Page 69: ...66 DYNAMAX HS FLOOR MOUNT...
Page 76: ...73 PART 15 ELECTRICAL DIAGRAMS 15 1 DM 80 299 INTERNAL WIRING DIAGRAM...
Page 77: ...74 15 2 DM 399 800 INTERNAL WIRING DIAGRAM...
Page 78: ...75...