27
Domestic Hot Water Programming Instructions
Modulation: Fixed Setpoint Operation (Standalone)
Description
Electrical Connection(s)
Programming Instructions
•
Boiler operates at a fixed
DHW setpoint
•
Modulates on boiler inlet
sensor (default)
•
Heat demand is generated
when Remote Operator is
closed.
DHW Sensor/ Stat, if required.
1)
Place both toggle switches in
LOCAL
2)
Press
and select Login
3)
Select Advanced Setup
4)
Select
DHW Config
Inlet Sensor operation
5)
Select
Demand switch = Sensor only,
and Press
6)
Select
Mod sensor = Inlet
, and Press
,
go to step 7
DHW Stat operation
5)
Select
Demand switch = DHW switch,
and Press
6)
Select
Mod sensor = Inlet,
and Press
,
go to step 7
DHW Sensor operation
5)
Select
Demand switch = Sensor only,
and Press
6)
Select
Mod sensor = DHW,
and Press
7)
Select
DHW Setpoint,
and enter desired setpoint using 5-way control
8)
Place right hand toggle switch setting to
REMOTE
for remote operation (if
required)