Figure 6.30 Power Rate Limit
Power Rate:016%
RateP_Sts-US:STOP
Over frequency load shedding Fstart range 60~62Hz, default setting 60.2Hz
Fstop can set the scope: 61-64Hz, the default setting 62Hz
.
Press the Enter key to select the mode or frequency
.
Press Up
/
Down to set. Press ESC to save the settings.
Figure 6.32 Freq
-
Watt
characteristic
f min
f nom
f start
f max
f stop
100
%
of
Available
Power
0
Grid
Frequency
6.7.8.3 Freq Derate Set
There are 5 derate modes in this menu. When operating under standard UL-1741 limits, modes
00 to 03 are disabled. Mode 04 is used for UL1741SA frequency derating setting. This sets the f
start and f stop point.
The default setting is 00, means this function is disabled.
Figure 6.31 Freq Derate Set
Derate
Mode
:
04
OV
-
F
-
Start
:
60
.
20Hz
6.7.8.4 10mins Voltage Set
This function is disabled and
not used for the US.
6.7.8.5 Initial Settings
In initial settings it will reset each work mode from 6.5.8.1 to 6.5.8.4 back to default.
This function is applicable by maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
Figure 6.33 Initial Settings
Work
Mode
Default
Power
Rate
Default
6. Normal operation
6. Normal operation
6.7.9 Restore Settings
Figure 6.34
Press the ENTER key to reset to factory defaults. Press the ESC key to return to the previous
menu.
Selecting “Restore Settings” displays the option shown below:
This section is applicable to maintenance personnel only.