2.7 PID & CONTROL PARAMETER PAGE
NOTE:
This page is password protected. See section 2.2.
Page five of the BMS-2000 controller display allows the adjustment of four parameters relating to
temperature control:
• Proportional, for PID control only
• Integral (Reset), for PID control only
• Derivative (Rate), for PID control only
• Dead Band, for ON/OFF control only
To make these adjustments:
1. Depress the ‘SELECT ITEM’ key repeatedly until the flashing cursor is in front of the parameter to be
changed.
2. Use the
and
buttons to change the value.
* Note: Displayed temperature units are specified at time of order.
NOTES:
• If the Rate or Reset values are equal to zero, they are disabled.
• All of the above parameters can be changed during startup or normal operation.
5. Prop. Band (%)
Bath: 50
Reset (Min/Rpt) Bath: 0.00
Rate (Min)
Bath: 0.00
D.Band (Deg C)
Bath: 2