16
of 42
Combustex BMS-2000 [5.03] Operations Manual -
3. CONFIGURATION
Phone:
403.342.4494
|
Web:
www.canaltaflow.com
For operational, technical or installation assistance, please contact us.
Call Us Toll Free:
1-855-226-2582
3.2 CONFIGURATION MENU ITEMS
Below are the BMS-2000 Version 5.03 CONFIG menu items and their options. See pp. 17 - 23 for a
description of each.
Item #
Sequencing Items
Available Options
Notes
1
Burners
1 / 2 / Dual Parallel / Dual Series
2
#1 T/C Flame 1st Level
0 - 800°C (32 - 1472°F)
Preset at 250°C (482°F)
N/A when “Flame Detection” config-
ured to “Contact” (flame rod, UV)
3
#1 T/C Flame 2nd Level
0 - 800°C (32 - 1472°F)
Preset at 450°C (842°F)
N/A when “Flame Detection” config-
ured to “Contact” (flame rod, UV)
4
#2 T/C Flame 1st Level
0 - 800°C (32 - 1472°F)
Preset at 250°C (482°F)
N/A when “Flame Detection” config-
ured to “Contact” (flame rod, UV)
5
#2 T/C Flame 2nd Level
0 - 800°C (32 - 1472°F)
Preset at 450°C (842°F)
N/A when “Flame Detection” config-
ured to “Contact” (flame rod, UV)
6
Trial for Ignition Timer
0 - 3.0 Minutes
Preset to .15 (9 sec) for “Contact”
Preset to 2 for “T/C”
Preset to 9 sec. when “Flame Detec-
tion” configured to “Contact” (flame
rod, UV)
7
Flame T/C 2nd Level Timer
0 - 5.0 Minutes
Preset to 3 for “T/C”
N/A when “Flame Detection” config-
ured to “Contact” (flame rod, UV)
8
Purge Timer
0 - 10.0 Minutes
9
Pre-purge
Yes / No
10
Ignition
Steady / Pulsed
11
Relight Attempts
0 / 1 / 2 / 3
12
Flame Detection
Contact / T/C / Aux Contact
13
Remote Start
Yes / No
14
Remote Stop
Yes / No
15
Power Failure Auto Relight
Yes / No
Safety Interlocks
16
Proof of Closure #1
Yes / No
17
Proof of Closure #2
Yes / No
18
Pilot
Continuous / Intermittent
19
Flame Status
Independent / Common
20
Fuel Low Pressure #1
Yes / No
21
Fuel High Pressure #1
Yes / No