Combustex BMS-2000 [5.03] Operations Manual -
3. CONFIGURATION
Phone:
403.342.4494
|
Web:
www.canaltaflow.com
For operational, technical or installation assistance, please contact us.
Call Us Toll Free:
1-855-226-2582
This sets the output mode for the pilot and main solenoid valves.
• Steady: Provides a constant voltage to the solenoid when on.
• Latching Pulse: For specialized solenoids only. This selection provides a pulse to open (latch) the
solenoid, and another pulse to close (unlatch) the solenoid.
Enables the set point input options on page two of the controller display. See section 2.4.
Enables the spare 4-20mA output to indicate bath temperature remotely.
This configures the behaviour of the controller display backlight.
• Steady On: Backlight stays on whenever the controller is powered up.
• Off: Backlight is disabled.
• Light Activated: Backlight will turn on when the ambient light becomes dim.
• Timed: Backlight will turn on when any key is pressed and will remain on for approx. five minutes.
This feature is not available in this version of the BMS software.
This sets the ‘USER’ password to a user-defined value. Factory default is set to ‘1313’. See section 2.2.
When a sharp RF spike is detected, the BMS-2000 will hold the previous setting. The typical setting is 20,
which gives approx. five seconds of hold time.
34
Control Output Mode
Steady / Latching Pulse
35
Remote Set Point I/P
Yes / No
36
Remote Temp. Indicate Out
Yes / No
37
Backlight
Steady On / Off / Light Activated / Timed
38
Audio
Yes / No
39
New Access Code
0 - 9999
40
R.F. Filter
0 - 1000