4
of 42
Combustex BMS-2000 [5.03] Operations Manual -
1. INTRODUCTION
Phone:
403.342.4494
|
Web:
www.canaltaflow.com
For operational, technical or installation assistance, please contact us.
Call Us Toll Free:
1-855-226-2582
1.3 EMERGENCY SHUTDOWN CAPABILITIES
The BMS-2000 can be configured to shut down when an unsafe or out-of-control condition exists.
1. Programmable HTSD limits on:
• Bath Thermocouple Input
• Process Thermocouple Input
• Stack Thermocouple Input
2. Standard dedicated discrete field device inputs preset at the factory:
• Remote Stop
• Remote Start
• Low Voltage
• Burner #1 Flame Sensor Failure
• Burner #1 Flame Failure to Relight
• Burner #1 Fuel Gas Low Pressure
• Burner #1 Fuel Gas High Pressure
• Aux. High Bath Temp. (Contact)
• Low Bath Level
• Burner #1 Main Valve Proof of Closure
3. Additional inputs for Dual Burner Systems:
• Burner #2 Flame Sensor Failure
• Burner #2 Flame Failure to Relight
• Burner #2 Fuel Gas Low Pressure
• Burner #2 Fuel Gas High Pressure
• Burner #2 Main Valve Proof of Closure
1.2 BURNER SEQUENCING
When initiating a start sequence, the BMS will open the pilot and energize the igniter for the trial for
ignition period and wait for the flame sensor to confirm a flame. Upon flame verification, the unit will
then go into “Normal Operation”. At this point, the BMS will energize the main burner and the flame
status output(s). The temperature control option will also become enabled (if configured).
Set points and the associated password protected timers are configurable in the BMS menu. Other
configurable options:
• Purge and Pre-purge
• Auto Relight on Flame Fail
• Auto Relight on Power Fail (unit will relight when power is restored)