OPERATION (SUITE) 

 

Installation typique

 - Référez-vous à la page 7

Démarrage

 

       Allumez le ventilateur et vérifiez ce qui suit. 

          •    Direction de rotation 
          Ampérage du moteur incorrect 

•         Vibration excessive 
•         Bruit inhabituel 
•         Tension ou alignement incorrect de la courroie 

 
Si un problème survient, éteignez le ventilateur et 
référez-vous à la section de dépannage pour découvrir 
la cause du problème. Le ventilateur doit être inspecté 
après 30 minutes, 8 heures & 24 heures d’opération afin 
d’assurer que toutes les fixations soient serrées et que 
l’unité opère correctement. 

MISE EN GARDE POUR L'ENTRETIEN

Débranchez et mettez en position ARRÊT toute l'alimentation électrique du ventilateur avant l'inspection 
ou l’entretien. Le non-respect des consignes de sécurité peut entraîner des blessures graves ou la mort. 

•   Le ventilateur doit être vérifié au moins une fois par année. Une vérification de routine régulière est recommandée 
     chaque deux ou trois mois. 

•   Lors du retrait ou de l’installation d’une courroie, ne forcez pas la courroie sur la poulie. Desserrez le support du 
     moteur pour que la courroie puisse être facilement glissée sur la poulie. 

•   La courroie, sur les unités entraînées par courroie, doit être retirée et soigneusement vérifiée pour des fissures, 
     la séparation des plis ou l'usure irrégulière. Une petite irrégularité dans la surface de contact de la courroie 
     entrainera un fonctionnement bruyant. Si l'un de ces défauts est apparent, la courroie doit être remplacée. En 
     même temps, vérifiez les poulies pour tout débris, bosses ou surfaces rugueuses qui pourraient endommager 
     la courroie. 

•   Une tension appropriée de la courroie est importante. Une courroie trop serrée peut causer une pression 
     excessive sur les roulements ce qui peut causer une défaillance prématurée des roulements et entraîner une 
     surcharge du moteur. Une courroie trop détendue entraînera un glissement qui brûlera les courroies. La déflexion 
     appropriée de la courroie doit être de 1/64 po (à mi-chemin entre les centres des poulies) pour chaque pouce 
     de portée de la courroie lorsqu'une force d'environ 5lbs est appliquée. 

•   L'alignement de la courroie doit être vérifiée pour s'assurer que la courroie tourne perpendiculairement aux 
     arbres rotatifs. Le moteur et les arbres d'entraînement doivent être parallèles. 

•   Une inspection périodique de toutes les fixations doit être effectuée pour s'assurer qu'elles ne se sont pas 
     desserrées à cause des vibrations. Une attention particulière doit être portée aux fixations fixant la roue à l'arbre 
     et à celles fixant l'arbre au roulement. 

•   Les paliers standards des ventilateurs entraînés par courroie sont lubrifiés d'origine. Ces roulements doivent 
     être lubrifiés semestriellement (plus fréquemment dans les applications sévères) à l'aide d'une graisse à base 
     de lithium de haute qualité. Avec l'unité en marche, ajoutez de la graisse très lentement, à l'aide d'un pistolet 
     graisseur manuel, jusqu'à ce qu'un léger filet de graisse se forme au niveau du joint. Veillez à ne pas déloger le 
     joint en lubrifiant excessivement ou en utilisant une pression excessive. Lorsque les roulements sont obstrués 
     de la vue, n'utilisez pas plus de trois injections avec un pistolet graisseur manuel. 

•   La poussière et saleté sur la surface extérieure du moteur, du panneau du ventilateur ainsi que de la roue 
     complète du ventilateur doit être enlevées à des intervalles déterminé par le degré de sévérité de l'application 
     afin d'assurer une durée de vie et sécurité appropriée. 

•   Pour des informations additionnelles sur la sécurité, référez-vous à la publication de l'AMCA 410-96, Pratiques 
     de sécurité recommandées pour les utilisateurs et les installateurs de ventilateurs industriels et commerciaux 

Summary of Contents for ADD

Page 1: ...nted to a wall require a different wall opening than fans mounted in cabinets or sleeves For specific dimensions refer to the submittal drawing for the specific fan configuration 2 Mount the fan in the opening with the fan panel directly over the load bearing support and if this is not practical angle supports must be provided to transfer the fan weight to the load bearing structure 3 Caution The ...

Page 2: ...event it from entering the shaft and propeller area 5 Disconnect switches are recommended and should be located near the fan in order to swiftly cut off power in case of an emergency and maintain complete control of the power source 6 Some motors may have to be removed in order to make the connections in the motor terminal box 7 Follow the wiring diagrams on the motor nameplate 1 Wall Fans Extend ...

Page 3: ...t the same time check the sheaves for chips dents or rough surfaces that could damage the belt The correct belt tension is important Too tight a belt will result in excess bearing pressure which can cause premature bearing failure and may cause the motor to overload too loose a belt will result in slippage which will burn out belts Proper belt deflection should be 1 64 half way between sheave cent...

Page 4: ... pulley Loosen the setscrews on the pulleys and remove from either the motor or fan shaft using a two or three jaw puller Remove any shaft imperfection such as setscrew mark using a file or emery cloth Install the replacement pulleys tightening all setscrews to the recommended torque rating see chart and ensuring that they are properly aligned Pulley alignment is achieved by moving the pulleys on ...

Page 5: ... the setscrews on the bearings and then tighten one setscrew on each bearing Loosely install the bearings on the bearing mount Rotate the shaft to find the center of free movement Install the propeller adjusting the bearing location to center the blade in the venturi Tighten the bearing bolts to the proper torque rating Turn the propeller by hand the propeller should rotate freely with the same re...

Page 6: ...ves Improper fan installation Static pressure higher than design MOTOR OVERLOADING Impeller rotating in the wrong direction Improper fan speed Defective motor Fan speed higher than design Filters missing TOO MUCH AIR Static pressure lower than design Fan speed higher than design Lack of electricity to the fan Fan wired improperly Broken or missing belt FAN DOES NOT OPERATE Missing or blown fuses O...

Page 7: ...excess of 50 pounds should also be supported using hanging rods or by supports placed underneath the fan Wall supply fan with cabinet back guard motorized shutter and weather hood The drawing below illustrates the typical installation of a supply fan with a cabinet back guard motorized shutter with end switch and weather hood in a masonry wall The installer shall provide angle iron framing and sui...

Page 8: ... defects in materials and workmanship to the extent that within a period of one year from the date of purchase CANARM Ltd shall either repair or replace at CANARM s option and unit or part thereof returned freight prepaid and found to be defective This warranty does not include any labour or transportation cost incidental to the removal and reinstallation of the unit at the user s premises Compone...

Page 9: ...e différente de ceux installés dans un armoire ou manchon Pour les dimensions spécifiques reportez vous au dessin de soumission pour la configuration spécifique du ventilateur 2 Montez le ventilateur dans l ouverture avec le panneau du ventilateur directement sur le support porteur et si cela n est pas pratique des supports d angle doivent être fournis pour transférer le poids du ventilateur sur l...

Page 10: ...r dans la zone de l arbre et de l hélic 5 Des sectionneurs sont recommandés et doivent être localisés près du ventilateur afin de couper rapidement l alimentation en cas d urgence et maintenir un contrôle complet sur la source d alimentation 6 Certains moteurs peuvent être retirés pour effectuer les connections électriques dans la boîte du moteur 7 Suivez le diagram de connection sur la plaque sig...

Page 11: ... est importante Une courroie trop serrée peut causer une pression excessive sur les roulements ce qui peut causer une défaillance prématurée des roulements et entraîner une surcharge du moteur Une courroie trop détendue entraînera un glissement qui brûlera les courroies La déflexion appropriée de la courroie doit être de 1 64 po à mi chemin entre les centres des poulies pour chaque pouce de portée...

Page 12: ...t un extracteur d engrenage à deux ou trois mâchoires Retirez tout imperfection à l arbre tel que marque de vis en utilisant une lime ou d une toile émeri Installez les poulies de rechange en serrant toutes les vis de réglage au couple nominal recommandé voir tableau et s assurer qu elles sont correctement alignées L alignement des poulies se fait en retirant les poulies de leur arbre respectif ou...

Page 13: ...age sur les roulements puis serrez une vis de réglage sur chaque roulement Installez les roulements sans serrer sur le support de roulement Faites tourner l arbre pour trouver le centre du mouvement libre Installer l hélice en ajustant l emplacement du roulement pour centrer la pale dans le venturi Serrez les boulons de roulement au couple nominal approprié Tourner l hélice à la main l hélice doit...

Page 14: ...ncue SURCHARGE DU MOTEUR Rotation de la turbine dans la mauvaise direction Vitesse incorrecte du ventilateur Moteur défectueux Vitesse du ventilateur plus élevée qu il est conçu Filtres manquants TROP DE VENTILATION Pression statique plus basse que celle concue Vitesse du ventilateur plus élevée qu il est conçu Perte de courant électrique au ventilateur Branchement électrique incorrect Courroie ma...

Page 15: ...ction arrière volet motorisé et hotte étanche Le dessin ci dessous illustre l installation typique d un ventilateur d alimentation avec un cabinet une protection arrière un volet motorisé avec interrupteur d extrémité et une hotte contre les intempéries dans un mur de maçonnerie L installateur doit fournir un cadrage avec cornière et des fixations appropriées boulons hexagonaux ou vis tire fond po...

Page 16: ... s appliquent GARANTIE CANARM Ltd garantit que chaque nouveau ventilateur est exempt de défauts de matériaux et de fabrication dans la mesure où dans un délai d un an à compter de la date d achat CANARM Ltd réparera ou remplacera au choix de CANARM toute unité ou partie de celle ci fret retourné prépayé et jugé défectueux Cette garantie ne comprend pas les frais de main d œuvre ou de transport lié...

Reviews: