14
Canarm Penta-Lite 5LEC Series
5
MOUNTING METHOD 2: ANGLE IRONS
5.6a Fasten Single Angle Iron to Roof Structure Mounting Points:
If installation requires double angle irons (i.e., span is greater than 8’(2.4m)), proceed to step 5.6b.
ATTENTION:
Do not tighten the hardware until the upper yoke has been mounted to the angle irons.
Proceed to step 5.7.
Grade 5 Hardware (customer supplied):
a.
(4) 1/2”-13 GR 5 Bolt (length varies by application)
b.
(8) 1/2” Flat Washer
c.
(4) 2-1/2” Square Washer (see diagram)
d.
(4) 1/2” Nylock Nut
Do not install the fan from a single purlin, truss, or bar joist.
Ne pas installer le ventilateur à partir d’une même purlin, botte, ou solives.
The angle irons must be fastened to the roof structure at each end.
Les cornières doivent être attachés à la structure de toit à chaque extrémité.
Fasten the angle irons to the roof structure mounting points at each end with customer-supplied Grade 5
hardware as shown.
Fixer les cornières aux points de fixation de la structure du toit à chaque extrémité fourni par le client 5
e année du matériel comme indiqué.
CAUTION/ATTENTION
!
2.5”
(6.4 cm)
9/16” Dia.
(1.4 cm)
2.5”
(6.4 cm)