IMPORTANT INFORMATION
2.1 Canarm Safety Components
Canarm fans are designed with redundant safety features to provide protection in the unlikely event
of a catastrophic failure. Follow installation instructions carefully when installing fans.
2.2 Fan Spacing’s and Placement
A standard ceiling fan should be mounted so that the bottom of the fans hub is 33 inches below the
bottom of the beam which it is mounted. Fan blades should be mounted between 10’ and 50’ above
the floor with optimum height between 20’-30’. If desired, extension bars are available to lower the fan
if needed. Avoid mounting fans directly below lights or skylights to avoid a strobe effect caused by
the moving blades.
When mounting a fan in an area where objects may be lifted or moved into the path of the fan,
Canarm recommends marking or painting hash lines on the floor to alert personnel of the above
movement of the fan.
The area within 15% of the diameter when the fan is at rest is considered “close clearance”. It is
extremely dangerous to mount the fans within “close clearance” of any object or path of object. We
strongly recommend not mounting the fan closer than 15% of its diameter to any object or its path. If
this is an issue, mounting extension bars and smaller fans are available from Canarm.
2.3 Fire Suppression Systems and Fan Placement
If installing Fans in a location where fire sprinklers are in place, do not interfere with their correct
operation. Fans should be located in the center of each sprinkler quadrant and no less than 3 feet
below the sprinkler. Review all codes applicable to sprinkler systems prior to installation; it is the
customer’s responsibility to see that the installation is completed to code and that it is correct.
2.4 Shielded Motor Cable
To minimize electromagnetic interference and stray voltage, Canarm recommends the use of
shielded input voltage cable. This shielded system reduces the likelihood of broadcasting and
receiving electronic noise which can interfere with radio and other sensitive equipment. This shielded
motor cable and the controller cable must be run in separate conduit at least 6 inches apart.
Electrical interference and stray voltages are the liability of the installer and are not covered by
Canarm under warranty.
2.5 Check Compliance with Federal, State, and Local Codes
Check all relevant codes to make sure product certifications, product listings, and building regulations
are met. Code compliance is the responsibility of the installer.