Canarm Tri-Lite 3LMPEC Series

10 

TROUBLESHOOTING

Set fan controller to 75% and 

“FWD”

Does the fan spin?

Is the LED light 

blinking?

Can the speed 

vary from 0-100% 

properly?

Switch the fan to 

“REV”. Allow it to 

ramp down and 

back up. 

Does it spin in 

reverse?

Yes

Check incoming power 

supply and compare to fan 

rating label. 

Note all delta power 

configurations are 

incompatible with 

Canarm fans.

Is the input voltage correct?

Fix incorrect

wiring.

Is the fan making 

any noise?

End of 

troubleshooting.

Yes

Yes

Yes

No

No

No

Check splices and wiring

at the controller. 

Is the Wiring correct? 

No

Fix incorrect 

wiring.

No

Yes

Yes

No

Check controller wiring 

sheet. 

Is the wiring correct?

Fix incorrect wiring.

No

Yes

Check all brackets and bolts. Ensure bolts are torqued to the 

proper rating and brackets are free to spin without collisions.

KEY

Start 

Question

Process

Question

Solution

Consult factory.

Yes

Continued on page 35

Continued on page 35

Consult factory.

No

Summary of Contents for Tri-Lite 3LMPEC

Page 1: ...Tri Lite 3LMPEC 6 8 HVLS FAN INSTALLATION MANUAL Custom Designed Reduced Maintenance STOL Technology...

Page 2: ...ordance with all applicable codes and standards including fire rated construction Failure to comply could result in personal injury electric shock death fire and or property damage Before attempting i...

Page 3: ...ils et ne pas les utiliser des fins autres que celles pr vues par le fabricant This unit has an unguarded impeller Do not use in locations readily accessible to people or animals Cet appareil poss de...

Page 4: ...WEIGHT 3L06MPEC 6 1 8M Fan 8 203 mm 60 1524 mm 9 229 mm 9 lbs 4 kg 3L08MPEC 8 2 4M Fan 8 203 mm 60 1524 mm 9 229 mm 10 lbs 5 kg 1 Fan Diagram 6 2 Important Information 7 3 Mounting Considerations 8 4...

Page 5: ...P A R T Y W IT H O U T T H E A U T H O R IZ A T IO N O F S K Y B L A D E F A N C O M P A N Y M A T E R I A L 1 1 S S 3 0 4 A L L D I M E N S I O N A R E I N I N C H E S U N L E S S O T H E R W I S E...

Page 6: ...ement efficiency by reducing drag MODEL 3L06MPEC 3L08MPEC DIAMETER 6 1 8M 8 2 4M BLADES 3 3 VOLTAGE INPUT 120 230 460 120 230 460 Model Number Ordering Format SERIES DIAMETER BLADES INPUT VOLTAGE PHAS...

Page 7: ...an closer than 15 of its diameter to any object or its path If this is an issue mounting extension bars and smaller fans are available from Canarm 2 3 Fire Suppression Systems and Fan Placement If ins...

Page 8: ...e event of this max torque being applied is unlikely and will only apply due to a failure of the variable frequency drive and its soft start technology 3 4 Safety Cable A Canarm fan should never be ru...

Page 9: ...t The spacing between multiple fans should be no less than 2 5x the fans diameter when measured from the center of the fans The mounting structure must be able to withstand the torque which is generat...

Page 10: ...pport Directly From Building Structure All mounting instructions assume that the building structure from which the fan will be hung is of sound construction undamaged and capable of supporting loads o...

Page 11: ...cture du toit chaque extr mit Fasten the unistrut to the roof structure mounting points at each end with customer supplied Grade 5 hardware as shown Fixez l unistrut aux points de fixation de la struc...

Page 12: ...nt destin es aux installations de faisceaux WARNING AVERTISSEMENT Do not install the fan from a single purlin truss or bar joist Ne pas installer le ventilateur partir d une seule panne botte ou soliv...

Page 13: ...Irons Together if span is longer than 8 If the angle iron span is 8 2 4m or less proceed to step 5 6a on the following page If the angle iron span is longer than 8 2 4m it is necessary to use double...

Page 14: ...e Washer see diagram d 4 1 2 Nylock Nut 2 5 6 4 cm 9 16 Dia 1 4 cm 2 5 6 4 cm Do not install the fan from a single purlin truss or bar joist Ne pas installer le ventilateur partir d une m me purlin bo...

Page 15: ...Nylock Nut Do not install the fan from a single purlin truss or bar joist Ne pas installer le ventilateur partir d une m me purlin botte ou solives The angle irons must be fastened to the roof struct...

Page 16: ...EXCLUSIVE PROPERTY OF SKYBLADE FAN COMPANY AND CANNOT BE REPRODUCED OR DISCLOSED TO ANY THIRD PARTY WITHOUT THE AUTHORIZATION OF SKYBLADE FAN COMPANY MATERIAL XXXXXXXX ALL DIMENSION ARE IN INCHES UNL...

Page 17: ...roceed to Hanging the Fan on pg 21 Clamping Plate Hardware supplied a 4 1 2 13x2 1 2 GR 5 Bolt b 8 1 2 Flat Washer c 4 1 2 13 Nylock Nut d 2 Clamping Plate a b c b d I Beam Flange Width Upper Yoke Mou...

Page 18: ...aced on both sides of the plate for each bolt 5 12 Pre Drill Angle Iron Brackets Holes Your angle iron should be cut to allow 1 2 1 27 cm clearance between the end of the angle iron and the purlin you...

Page 19: ...the purlin brackets 5 15 Attach Upper Yoke to Angle Iron Attach the upper yolk to the angle irons using the provided 1 2 grade 5 bolts washers and nylock nuts See section 5 7 Attach Upper Yoke to Ang...

Page 20: ...1 2 Flat Washer c 2 1 2 16 Nylock Nut 6 2 Secure Upper Safety Cable Secure the safety cable to the I beam or angle iron by wrapping the safety cable around it threading the cable through the 17 32 ope...

Page 21: ...vitesses ce qui peut entra ner des dommages ou une dur e de vie raccourcie Ne pas installer le niveau annulera la garantie du fabricant WARNING AVERTISSEMENT 6 3 Attach the Motor to extension tube At...

Page 22: ...erence Eye Hook illustration on page 23 1 Slide the unlooped end of the guy wire through the eye hook 2 Feed the wire through the loop on the other end of the wire 3 Pull tight so the wire tightens on...

Page 23: ...ing a Beam Clamp b Eye Hook c Gripple Wire Loop Gripple Maximum Angle Gripple Hook Tab Motor Make certain all electrical cords are not obstructed by guy wires Assurez vous que tous les c bles lectriqu...

Page 24: ...THE EXCLUSIVE PROPERTY OF SKYBLADE FAN COMPANY AND CANNOT BE REPRODUCED OR DISCLOSED TO ANY THIRD PARTY WITHOUT THE AUTHORIZATION OF SKYBLADE FAN COMPANY MATERIAL XXXXXXXX ALL DIMENSION ARE IN INCHES...

Page 25: ...IS THE EXCLUSIVE PROPERTY OF SKYBLADE FAN COMPANY AND CANNOT BE REPRODUCED OR DISCLOSED TO ANY THIRD PARTY WITHOUT THE AUTHORIZATION OF SKYBLADE FAN COMPANY MATERIAL XXXXXXXX ALL DIMENSION ARE IN INC...

Page 26: ...be positioned on top of the boomerang bracket of the blade previous First install all boomerang brackets and hardware by hand tightening Second tighten the blade bolts individually with a 1 4 allen wr...

Page 27: ...are Kit supplied a 3 BTN Cap Screw 10 32 X 3 8 Wingtip Wingtip Blade 2 2 3 3 4 4 A B C D Page DRAWN DAT XX XX XX DRAWN BY XX THIS DRAWING IS THE EXCLUSIVE PROPERTY OF SK DISCLOSED TO ANY THIRD PARTY W...

Page 28: ...c voltages supply voltage variations voltage dips and frequency time deviation Canarm n est pas responsable des perturbations de tension en r f rence explicite aux interf rences magn tiques lectroniqu...

Page 29: ...rom line inputs at the fan controllers disconnect L1 L2 L3 Wait three 3 minutes for capacitors to discharge to safe voltage levels Darkened display LEDs are NOT an indication of safe voltage levels Fa...

Page 30: ...stallation CAUTION ATTENTION IMPORTANT Check that the correct input voltage is being sent to the fan See rating labels on the motor for acceptable voltage A blown fan due to incorrect input voltage is...

Page 31: ...Input Power Cable Wiring Schematics IMPORTANT Grounding of the incoming power on the motor is required NOTE Canarm suggests using a field supplied fused disconnect switch 1 Phase Voltage 120V 3Ph 230V...

Page 32: ...o a Fire Alarm Panel If the installation of the fan is required to be wired to a fire alarm emergency shut off an external relay will have to be placed by a fire suppression specialist between the vol...

Page 33: ...ding at the motor controller and from the controller to the supply b Do not run your controller and sensitive equipment on the same power line c Install properly sized EM RFI filter d Contact Customer...

Page 34: ...h Canarm fans Is the input voltage correct Fix incorrect wiring Is the fan making any noise End of troubleshooting Yes Yes Yes No No No Check splices and wiring at the controller Is the Wiring correct...

Page 35: ...lt may be occurring a line reactor may need to be placed to reach correct voltage If the voltage is low at splice of the fan motor Under volt may be occurring a line reactor may need to be placed to r...

Page 36: ...Aluminum PP 138 Motor H30 3 Ph PP 015 5 Extension Bar 5 ft Aluminum PP 172 6 6 Mini Blades PP 027 Chassis Silver PP 172 8 8 Mini Blades PP 029 Chassis Bottom Plate Steel PP 182 Red Wing Tip BP 031 Pur...

Page 37: ...ury to persons during cleaning and user maintenance Risque d incendie de choc lectrique ou de blessures lors du nettoyage et de l entretien par l utilisateur Disconnect the appliance from the power su...

Page 38: ...38 Canarm Tri Lite 3LMPEC Series 12 USER SERVICING INSTRUCTIONS Maintenance Log Replacement Part List DATE MAINTENANCE PERFORMED REPLACEMENT PARTS REQUIRED PART NO DESCRIPTION...

Page 39: ...Canarm Tri Lite 3LMPEC Series 39 NOTES...

Page 40: ...LIM3LMPEC 0123_03 PHONE 1 613 342 5424 FAX 1 800 263 4598 E Mail hvacsales canarm ca www canarm com...

Reviews: