background image

Back to Back Assembly:

Where two rows of racks are required, two rack assemblies may be 

installed back to back.

Frame Location: 

Locate back to back frames relative to each other as shown in  

Figure 14, such that the rear cross brace attachment holes align 

for the two adjoining frames (The frames will be facing opposite 

directions). All braces must be installed, as described previously, 

except that a single bolt may be used to connect the front and 

rear frames and respective cross braces. The ½-13 x 1.50” long 

bolt supplied with the rack is to be replaced by a ½-13 x 2 ¼” long 

(supplied with racks).
When placed back to back, there must be enough distance between 

the frames to allow all of the braces (four total) to be installed. The 

“X” distance between anchor bolt holes should be as noted in Table 

1 (see Figure 15).

Two step standard racks placed back to back do not need to have 

the frames bolted together. For 2 step EP1 racks a bolt assembly is 

required (C&D part # REO5253 purchased separately). Contact C&D 

for more details.

The EP racks have anchor bolt slots with a 1.06” x 0.69” (26.9 mm x 

17.5 mm) for One Tier and Two Step rack models and a 1.06” x 0.81” 

(26.9 mm x 20.6 mm) for Two Tier and Three Tier rack models.  

The distance between the anchor bolt locations when the racks are 

placed back to back is shown in Table 1 and Figure 15.

Note: There may be a de-rating of anchor bolt load ratings due to the 

proximity of holes. Reference anchor bolt manufacturer’s data for 

information.

ADDITIONAL INSTRUCTIONS FOR MULTI-RACK ARRANGEMENTS

Table 1

Front of Rack A

Front of Rack B

Back of

Racks A & B

Back to Back Assembly

Anchor Bolt

Center Distance

"X"

Anchor Bolt distance (center to center)

racks back to back

NOTE

:

Anchor selection is determined by the anchor type, the diameter of the anchor, the depth of embedment 

and anchor spacing. The selection of the anchor bolt must be reviewed by a structural engineer to ensure 

that the racks will meet the seismic rating for the EP racks.

FIGURE 15

FIGURE 14

RDC Rack

Inches

mm

Inches

mm

1 Tier

3.95

100

4.32

110

2 Tier

3.88

99

4.08

104

2 Step (Std & EP1)

3.63

92

5.67

144

2 Step (EP2)

4.01

102

4.26

108

3 Tier (EP1)

4.64

118

3.88

99

3 Tier (EP2)

4.26

108

4.24

108

"X" Distance

See Figure 15

Anchor Bolt Distance

RS02098/1011/CD   

 

 

 

 

 

 

 

                    www.cdtechno.com

Summary of Contents for RDC Series

Page 1: ...e codes Do not attach rack to walls without consulting the appropriate structural engineer Mounting holes are provided in the base of each frame All frames must be secured to floor using all anchor bo...

Page 2: ...vide floor mounting hardware SEE PAGE 7 8 FOR LOCATION OF MULTI RACK ARRANGEMENTS 4 Initial Assembly Anchor bolt washers P N RD05084 or RD05100 for three tier racks are supplied with the EP racks Each...

Page 3: ...NSTRUCTIONS FOR RDC STANDARD AND EP RACKS 6 Leveling Check that the rack is level and square Torque down all bolts First torque the cross brace bolts to 55 65 ft lb 75 88 N m then torque the rail to f...

Page 4: ...ount of water unscented talcum or Dow Corning III may be applied to the rail cover to help reduce friction For rows having an odd number of batteries the center of the first battery installed will mat...

Page 5: ...d Cover Serrated Nut Corner Bracket Assembled Side Restraint Rail and Cover Support Rail and Cover End Restraint Rail and Cover End Rail Restraint Rail s and Corner Brackets assembly is reversed the e...

Page 6: ...cable assemblies as determined by the battery arrangement Refer to Battery Installation Manual RS 1476 for more detail on battery connection and initialization charge Follow Battery Installation Manu...

Page 7: ...anchor bolt slots with a 1 06 x 0 69 26 9 mm x 17 5 mm for One Tier and Two Step rack models and a 1 06 x 0 81 26 9 mm x 20 6 mm for Two Tier and Three Tier rack models The distance between the anchor...

Page 8: ...19 7899 800 543 8630 customersvc cdtechno com www cdtechno com End to End Rack Installation Instructions Where a continuous rack string is required two racks may be installed adjacent in length Frame...

Reviews: