FAULT FINDING

A selection of common known problems and solutions are listed below.

Problem

Cause

Answer

Programmed 7-5 but zone
1 won’t isolate in night set.

Have not MANUALLY
isolated zone when setting
panel.

When night setting enter
code * 0 * 1.

Tamper won’t clear with lid
on.

Tamper loop open.

Check 24hr tamper, sounder
tamper, and all devices for an open
tamper loop.

PA won’t work on the
keypad.

Not holding * and # long
enough or option not
enabled

Be sure to HOLD * and # until the
alarm activates. Enable option 7-6.

Mains light not on.

No mains.

Check fuse & mains supply.

Battery not taking over
after mains fail.

Battery fuse blown, battery
not connected, or flat
battery.

Connect battery and check 1A
battery fuse. Fit new battery.

Remote keypad not
responding.

Incorrect wiring.

Check wiring. C to C and D to D.

Zones failing to activate.

Incorrect wiring.

Make sure the devices are wired in
series NOT parallel.

Zone activates during
entry.

Seeing an alarm zone on
entry or deviating from
entry route.

Make sure all zones on entry route
are programmed with walk-through.
Don’t deviate.

Zone activates even in
day mode.

Programmed to PA or
FIRE.

Reprogram the zone to be an alarm
zone or similar.

If you are still experiencing problems then contact our technical helpline with information at

hand regarding your situation. If your problem stems from wiring, you may be required to write

down wiring instructions, so have a pen and paper at hand.

General questions & Answers

Question

Answer

Can two bell boxes be used on the
system?

Yes, make sure tampers are in series and do not
exceed the current limit.

Can a “sound bomb” be installed?

Yes, connect between AUX+ and S-. Be sure not to
exceed maximum current rating.

Can the engineer set the panel
without the need of the user code?

Yes, if the engineering code is entered, the panel will
start the set.

How many PIRS can be connected
to a zone?

As many as current supply will allow. Zone resistance
should not exceed 50 ohms.

What happens if a zone is still in
fault when the bell cuts off?

The panel will re-arm. Any zones in fault will be
temporality isolated, and they will re-arm when the
fault clears.

Will there be any further alarms?

Any further alarm activations will trigger the bells
again for the selected time.  If any zone activates
three times in succession, it will be isolated. Alarms
can still occur from other zones.

Summary of Contents for SECURIT ST800L+

Page 1: ...INSTALLATION MANUAL SECURIT 800L CONTROL PANEL ST800L...

Page 2: ...mote Keypad 7 POWERING UP 7 Initial Power Up 7 PROGRAMMING 8 Exit Time 8 Entry Time 8 Sounder Duration 9 Night Set Home Set Exit Time 9 Circuit Programming 10 Extended Programming Options 10 Home Set...

Page 3: ...e the unit will be repaired and returned free of charge PRODUCT DESCRIPTION The Securit 800L is an 8 zone programmable microprocessor control panel using state of the art technology and manufacturing...

Page 4: ...eight 2 7 kg Excluding Battery Stand by Battery 7 0Ahr max valnve regulated lead acid Standby Time load dependent 24 hrs with 2 8Ahr nom 60 hrs with 7 0Ahr nom based on panel keypad 2 PIR 40 20 25 25m...

Page 5: ...corrected by a qualified electrician to ensure continued safe operation CAUTION Under certain circumstances the transformer metalwork can reach 70 C This is normal and well within prescribed limits B...

Page 6: ...hat the sounder trigger is applied negative Negative ring ST Strobe switched negative trigger S Sounder switched negative trigger Sounder hold off strobe positive supply Sounder hold off supply sounde...

Page 7: ...MUST wire in series See the Glossary for series and parallel examples POWERING UP INITIAL POWER UP Note Keep the lid off the main control panel in order to enter engineer mode Alternatively you can e...

Page 8: ...e lid of the panel or keypad PROGRAMMING Once the panel is in engineering mode the following options are available EXIT TIME 3 0 Range 10 90 seconds Enter 3 0 The factory default is 30 seconds You can...

Page 9: ...he selection The accept tone then sounds Note If extension speakers are fitted in Night and Home set you can alter the exit sounder volume by the control on the PCB marked VOLUME Option Option Results...

Page 10: ...ULL SET Turn and hold for 2 0 seconds PART SET EXTENDED PROGRAMMING OPTIONS 7 Range 1 8 The control panel offers the following additional options Enter 7 1 Disables sounder and strobe in Night Set Ent...

Page 11: ...subsequent alarms as well as isolated circuits First to alarm is shown by the LED being ON continuously Subsequent alarms are shown by the LED s flashing and isolated circuits are shown by LED s puls...

Page 12: ...code to prevent unauthorised alteration To enable this the engineer code must end in 9 If the engineer code is lost it will not be possible to enter engineer mode the PCB will need to be replaced Thi...

Page 13: ...m the exit time drops to 8 seconds as soon as the EXIT door has closed thus avoiding the preset exit time FULL SET KEYSWITCH Allows the panel to be set unset and reset through zone 8 Note The keyswitc...

Page 14: ...RY VOLTAGE V AUX VOLTAGE V INSTALLED BY SOUNDER CONNECTIONS CONTROL PANEL ST S R SONADE 2000 STROBE B D A T FLASHGUARD XL STROBE SIREN SUPPLY SUPPLY TAMPER OUT STARLIGHT 2000 ST R H H RTN ACTIVEGUARD...

Page 15: ...ne activates even in day mode Programmed to PA or FIRE Reprogram the zone to be an alarm zone or similar If you are still experiencing problems then contact our technical helpline with information at...

Page 16: ...STEMS is always endeavouring to improve quality and specification of all its products and may alter or amend this product and instructions without notice C K Systems Ltd Unit 24 Walkers Road North Moo...