background image

Back Terminal view (TCS model)

Back Terminal view (Standard model without TCS)

Remote Block (DI-2)

Remote Trip (DI-1)

DI-Common

06

Summary of Contents for CSDPR-V2-300

Page 1: ...DPR V2 300 R37QRG000132 Quick Reference Guide Q RG This QRG will help you step by step installation operation and programming procedure Please go through all the instructions carefully prior to implem...

Page 2: ...only when CT current is present orAux supply is available with other power sources only the relay display HMI will be available In the absence of Aux supply Battery voltage USB LCD will get energized...

Page 3: ...ement Key Enter Key USB port for PC Laptop communication Fault Reset Key Manual Reset on pressing for 2 sec See Description B MHT Ready MHT Ready LED Down Scroll Increment Key Battery Cover Remove bat...

Page 4: ...DI 1 CB Open CB Close B1 B1 B3 B3 B2 B2 B4 B4 Flag Indicator Flag Indicator Trip Coil Trip Coil TF TF TC TC TF TF TC TC DO 1 DO 1 A7 A7 A8 A8 DO 2 DO 2 A5 A5 A6 A6 Latch Latch Operates with only Aux...

Page 5: ...eous protection 50 Earth time Over Current 51N Earth time Instantaneous Over Current 50N Circuit Breaker Failure protection 50BF Switch onto fault SOTF Trip circuit supervision 74TC Fault Record 05 Ev...

Page 6: ...Back Terminal view TCS model Back Terminal view Standard model without TCS Remote Block DI 2 Remote Trip DI 1 DI Common 06...

Page 7: ...the Battery cover by twisting it on the right side as shown in the Left image Remove the Sticker placed on Battery to start the unit with Battery Replace the prescribed 1 2 AA size suitable battery w...

Page 8: ...B cable type A A Measuring Input Rated data Rated current IN 1A Frequency FN 50 60 Hz Measurement Measurement of Phase Earth current starts from 5 Rated auxiliary Universal L 18V 60V DC voltage UH H 8...

Page 9: ...ct Relay Specs Number of relays 4 DO contacts DO 1 2 DO1 DO2 are user programmable configurable available for I I le Ie CBFP only with Auxiliary supply Unbalance U0 Remote DI all faults Relay contacts...

Page 10: ...Inverse Graph Representation Inverse Time characteristics 10...

Page 11: ...ot for the users How to do Settings Note Menu Model Dependent EDIT VIEW ForActive Group Selection of Parameter GROUP SELECT Protection Related Parameter Menu PROTECTION Cold Load Protection Menu COLDL...

Page 12: ...DEFT Trip timing for SC Protection Ie 0 05xIn Earth Over current Pickup tie 0 01 Inverse Trip Time te 0 05s DEFT Trip Time Ie 0 01xIn Earth High set Pickup te 0 05 DEFT Trip timing Earth High SOFTpk...

Page 13: ...VENT NUMBER ERASE EVENTS BACK From Menu 1 From Menu 1 From Menu 1 On selecting DO ASSGNMNT by pressing ENTER key User can see the list of all the parameter by using the scroll keys Press ENTER to sele...

Page 14: ...roll keys Press ENTER to select the desired Parameter use SCROLL keys to Edit the selected one If the user change any of the setting It is required to save the changes by pressing ENTER key and than s...

Page 15: ...ting the other options by pressing ENTER key EDIT RTC HOUR 11 MIN 26 SEC 59 DATE 23 MONTH 08 YEAR 2019 BACK On selecting EDIT RTC Menu user can set the Date Month Year Day Hour Minute Second by using...

Page 16: ...cted Two Digital outputs Relays work only in presence of Auxiliary supply To recheck the Digital output operation Go to Trip Test Menu Enter in the LED RLY TST option test the Relays Tripping coil not...