background image

CANNON

CANTERBURY INBUILT

CANTIB-02-NG AND CANTIB-02-LP

TO SUIT MOCK FIREPLACE INSTALLATIONS

INSTALLATION INSTRUCTIONS FOR FITMENT

INTO A COMBUSTIBLE ENCLOSURE

This heater is for use with Natural and Propane gases.

Read these instructions in conjunction with heater

installation instructions

SPACE
HEATER

GAS LOG

FIRE

REF:

 F2663-E 

CANTERBURY IB MOCK INSTALLATION INSTRUCTION.CDR

REVISION “E”                                                                                          DATED: APRIL 2007

Summary of Contents for CANTERBURY CANTIB-02-LP

Page 1: ...O SUIT MOCK FIREPLACE INSTALLATIONS INSTALLATION INSTRUCTIONS FOR FITMENT INTO A COMBUSTIBLE ENCLOSURE This heater is for use with Natural and Propane gases Read these instructions in conjunction with heater installation instructions SPACE HEATER GAS LOG FIRE ...

Page 2: ...COMMENDATIONS age 2 MOCK CAVITY DIMENSIONS age 3 P 4 ag OVERALL DIMENSIONS OF INSERT CABINET P e ge FITMENT OF SPACER BRACKETS AND BLANKET Pa 5 INSTALLATION INTO WALL CAVITY METHOD A Page 6 7 P INSTALLATION INTO COMBUSTIBLE CAVITY METHOD B age 8 P MAINTENANCE age 9 ...

Page 3: ...ELF WITH THE CORRECT INSTALLATION METHODS CORRECT FLUE DESIGN AND ALLOWANCE FOR VENTILATION MUST BE CONSIDERED AVOID THE USE OF FLUE BENDS IF POSSIBLE ALWAYS ALLOW FOR THE COMPLETE REMOVAL OF THE HEATER WITHOUT ANY DIFFICULTIES AND MAKE SURE THAT THE FLUE IS RIGID AND SELF SUPPORTING THE BOTTOM LENGTH OF THE FLUE MUST FIT INSIDE OF THE ADAPTING PIECE THE FLUE ADAPTING PIECE MUST BE A SLIP FIT OVER...

Page 4: ...HEATER WILL NEED TO BE CONSTRUCTED THE HEATER MUST SIT ON A SOLID SEALED BASE AND THE ENCLOSURE MUST BE SEALED FROM ANY DRAUGHTS AND BE INSULATED AS NECESSARY TO ELIMINATE LOW TEMPERATURES OUR BROCHURE ILLUSTRATES AN ENCLOSURE CONSTRUCTED TO AN EXISTING ROOM WITH A SOLID FLOOR AND CEILING ANY OTHER ENCLOSURE MUST HAVE THE SAME CHARACTERISTICS OF BEING SEALED FROM ANY DRAUGHTS AND SUITABLY INSULATE...

Page 5: ...USTIBLE SURFACES 20 mm CLEARANCE FROM BOTH TOP AND SIDE SURFACES 50 mm CLEARANCE FROM REAR 100 mm CLEARANCE BETWEEN SIDE OF THE HEATER FRONT AND COMBUSTIBLES ADDITIONAL CLEARANCES ARE SPECIFIED IN THE HEATER INSTALLATION INSTRUCTION BOOKLET FIG 10 FIG 2 DEPTH OF CAVITY HEATER ADAPTOR FLUE CLEARANCE MIN 450 mm 300mm 125mm 25mm MAX 505 mm 300mm 125mm 80mm ...

Page 6: ... DEPTH WITH TRANSITION ADAPTOR FITTED 425 mm 620 mm 350mm 425mm THE HEATER FOR INSTALLATION INTO A MOCK FIREPLACE IS SUPPLIED WITH THE FOLLOWING PARTS SEE FIG 5 F1417 FLUE TRANSITION ADAPTOR F1404 REAR BRACKETS F1405 TOP SIDE SPACER BRACKETS F1406 INSULATION BLANKET F2663 INSTRUCTION BOOKLET 1 OFF 2 OFF 4 OFF 1 OFF 1 OFF ...

Page 7: ...R CABINET ON DIAGONAL CORNERS AS SHOWN SEE FIG 5 3 POSITION INSULATION BLANKET ON HEATER TOP ALIGNED WITH EDGES SECURE WITH MASKING TAPE AS SHOWN SEE FIG 5 FIXING SCREWS No8 x 3 8 SELF TAPPING D I A G O N A L C O R N E R S 563 mm TO ENTRE LINE C O A C R E R D I A G N L O N S TOP SIDE BRACKETS ATTACHED INSULATION TO TOP OF THE HEATER WITH MASKING TAPE FIG 5 TRANSITION ADAPTOR REAR BRACKET INSULATIV...

Page 8: ...THROUGH HEADER FLANGES AT STUD CENTRES AND USE CLOUTS OR SCREWS TO ATTACH TO WALL 6 MEASURE DISTANCE FROM FLOOR TO TOP OF FLUE OUTLET OF THE HEATER 7 ADJUST ELBOW TO THE DISTANCE MEASURED PLUS 2 mm AND TIGHTEN SCREW ENSURE FLUE ELBOW IS HORIZONTAL 8 BEND TABS IN AT THE BASE OF THE TWIN SKIN FLUE AND LOWER TWIN SKIN FLUE DOWN THE WALL CAVITY 9 SLIDE TOP PLATE FLUE SUPPORT OVER TWIN SKIN FLUE CENTRA...

Page 9: ...TE FLUE SUPPORT FLUE ADAPTER FLASHING FLUE CLAMP FLUE COWL APPROVED TO AG604 ROOF CLADDING 100 mm DIA FLUE PIPE MAINTAIN 25 mm CLEARANCE BETWEEN FLUE AND WOODWORK WALL CLADDING 12 mm FROM BOTTOM OF WALL CLADDING TO TOP OF HEATER MEASURE DISTANCE FROM FLOOR TO TOP OF HEATER FLUE OUTLET PLUS 2 mm COWL FIT 3 SCREWS SMALL DIA END WITH SWAGE TOP PLATE FLUE SUPPORT FLUE ADAPTER SINGLE SKIN FLUE Page 7 F...

Page 10: ...FROM ALL COMBUSTIBLES INSULATION BLANKET HEATER 100 mm DIA SINGLE SKIN FLUE FLUE TO FIT INSIDE OF SPIGOT FIT TWO LENGTHS OF VERTICAL FLUE 1 8 M BEFORE FITTING ANY BENDS IF BENDS ARE USED FIT INSIDE OF FLUE PIPE USE NO MORE THAN TWO BENDS IN THE TOTAL FLUE RUN AND MAINTAIN AT LEAST 250 mm OF STRAIGHT FLUE PIPE BETWEEN THE BENDS FLUE TO BE SUPPORTED INDEPENDENTLY OF THE APPLIANCE FLUE CONNECTION 125...

Page 11: ...MAINTENANCE IF YOUR HEATER REQUIRES ATTENTION CONTACT SAMPFORD AND STAFF PTY LTD ON PH 1300 727 421 or FAX 1300 727 425 Page 9 7 ...

Page 12: ...REF F2663 E CANTERBURY IB MOCK INSTALLATION INSTRUCTION CDR REVISION E DATED APRIL 2007 ...

Reviews: