EdgeAccess Universal Chassis System

UCS 1000

2-1

Chapter 2
Installing and Setting Up the Chassis

This section describes how to set up the chassis, including power supply options, mounting, cabling,
and powering up the chassis.

Caution:

Equipment intended only for installation in a RESTRICTED ACCESS LOCATION
accessible only to electrically skilled persons and electrically instructed persons with
the proper authorization.

1. Plan the installation, considering these characteristics:

 

Place the chassis within 7 ft. (2.134 m) of the power source.

 

Plan to use one or more of these locations for the connection to Earth Ground:

 

The bonding lug on the rear of the chassis, near the bottom

 

The grounding prong on the AC power cord

 

The ground side of the -48 VDC terminal strip

 

The mounting hardware for the rack, if the rack is tied to Earth Ground

 

Place the chassis adjacent to other Canoga Perkins or related equipment.

 

Allow room for the cable management bracket(s) that channel the cables, allowing slack in the
cables and providing a surface for securing with a tie-wrap.

 

Leave at least a 1U space between the chassis any other equipment for adequate ventilation; a
positive airflow cabinet is recommended.  If the environment has little air flow or the chassis and
other equipment are closely spaced or heavily loaded, use the optional fan tray to ensure adequate
cooling.  For details, contact Canoga Perkins Technical Support.

2. Unpack the chassis and inspect all components.  Save the shipping carton and packing materials

in case you need to return the equipment to the manufacturer.  Appendix A provides information
for Return Material Authorization (RMA).

3. Set the chassis and signal ground option located on the rear of the chassis, near the top.  See

Figure 2.

 

To isolate the grounds for the chassis and the signal, screw the shorting plug into
CS_GND/SIG_GND ISOLATED.

 

To connect the grounds for the chassis and the signal, screw the shorting plug into
CS_GND/SIG_GND CONNECTED.

Figure 2.  Chassis and Signal Ground Options

Summary of Contents for EdgeAccess UCS 1000

Page 1: ...Universal Chassis System UCS 1000 User Manual...

Page 2: ......

Page 3: ...00nm 1600nm L utilisation d instruments optiques par exemple un collimateur optique avec cet quipement peut s av rer dangereuse pour les yeux Proc der des contr les des ajustements ou toute proc dure...

Page 4: ...any time without prior notification Every effort has been made to keep the information in this document current and accurate as of the date of publication or revision However no guarantee is given or...

Page 5: ...tory Compliance 3 2 Appendix A Limited Warranty A 1 List of Figures Figure 1 Populated UCS 1000 1 1 Figure 2 Chassis and Signal Ground Options 2 1 Figure 3 Mounting Bracket on Chassis 2 2 Figure 4 Cha...

Page 6: ...EdgeAccess Universal Chassis System UCS 1000 iv...

Page 7: ...gement The optional Chassis Management Module CIM provides alarm relays and management for multiple chassis in the domain Individual application modules provide various network and transmission functi...

Page 8: ...or 2 15 1 None 14 1 1 13 2 None 12 By itself the chassis cannot generate a power failure alarm If you install a CIM which includes alarm circuitry and connectors you can connect an external device to...

Page 9: ...ment Allow room for the cable management bracket s that channel the cables allowing slack in the cables and providing a surface for securing with a tie wrap Leave at least a 1U space between the chass...

Page 10: ...racket then attach that bracket to the rack with four screws see Figure 3 To place the chassis on a flat secure surface turn the chassis upside down mount the self adhesive feet at the four corners of...

Page 11: ...D CID0 CID1 CID2 1 Closed Closed Closed 2 Open Closed Closed 3 Closed Open Closed 4 Open Open Closed 5 Closed Closed Open 6 Open Closed Open 7 Closed Open Open 8 Open Open Open 8 Set SW1 CH DCPS to ma...

Page 12: ...y firmly into the slot and tighten the captive Philips screws to secure it Caution In a redundant DC configuration both DC sources must have the same ground potential 11 Make sure the external power s...

Page 13: ...tion DC Power Off No power Amber Soft start delay Green Normal operation AC Power Off No power Green Normal operation The chassis is ready for installing the system modules All modules are hot swappab...

Page 14: ...EdgeAccess Universal Chassis System UCS 1000 2 6...

Page 15: ...tion cooling 0 50 C with fan tray Humidity Up to 95 non condensing Power AC 150 W 90 to 264 VAC 2 A max 50 60 Hz input Front panel switch rated at 4 A continuous and 5 A up to 25 sec DC 150 W 36 to 58...

Page 16: ...ce ETL cETL UL 60950 CAN CSA C22 2 No 60950 EN IEC 60950 IEC 60825 1 FCC Part 15B IC 003 VCCI Class A C Tick AS NZS 3548 EN 55022 Class A EN 61000 3 2 EN 61000 3 3 EN 50024 FCC Part 68 IC CS 03 TS 016...

Page 17: ...cified rating normal wear and tear of mechanical components or alteration or repair by anyone other than Canoga Perkins or its authorized representative If the user is unsure about the proper means of...

Page 18: ...LUSIVE REMEDY AUTHORIZED RESELLERS ARE NOT AUTHORIZED TO EXTEND ANY DIFFERENT WARRANTY ON CANOGA PERKINS BEHALF Return Policy Customer must obtain an RMA Return Material Authorization number from the...

Page 19: ......

Page 20: ...CANOGA PERKINS CORPORATION 20600 Prairie Street Chatsworth California 91311 6008 USA Phone 818 718 6300 FAX 818 718 6312 Web Site www canoga com Email fiber canoga com...

Reviews: